terminal, shall be not less than 3m in actual vertical height. When calculated in
accordance with BS 5440: Part 1 Annex A, the minimum
equivalent
height of the flue
shall be 2.0m of 125mm dia. flue pipe.
3.
The flue must not be used for any other appliance or application.
4.
Proprietary terminals must comply with BS 715 or BS 1289. Any terminal or
termination must be positioned in accordance with BS 5440 Part 1 to ensure that the
products of combustion can be safely dispersed into the outside atmosphere. Where
the appliance is connected to an unlined brick chimney it is generally unnecessary for
the chimney pot to be replaced or for a terminal to be fitted unless the flue has a
diameter smaller than 170mm.
3.12 Propane fires.
Propane gas appliances must not be installed in a room that is built entirely below
ground level (See BS 5871 Part 2).
4. PACK CONTENTS
Carefully remove all the contents. Check that all the listed parts are present and in
good condition (See figure 7).
Appliance contains:
1
Burner & Convection box unit.
1
Inlet ‘T’ connector with pressure test point including nut and olive for 8mm inlet
pipe.
1
Flue restrictor.
3
Screws (For fitting the flue restrictor).
1
Rear Ceramic wall support bracket
2
Screws (For fitting the rear ceramic wall support bracket).
1
Ceramic back wall.
1
Pair of ceramic side walls.
2
Small “U” seals for the convection box side flanges.
1
Strip of floor sealing tape.
6
Fibre wall plugs.
4
Woodscrews.
2
Fire retaining cables.
2
Cable clamps.
4
Eyebolts.
1
Rubber grommet.
1
Knurled shouldered screw for control linkage fixing.
2
M4 Machine screws (For fascia securing).
1
PP3 battery.
1
Smoke match tube.
1
Length of self adhesive foam seal.
Page 16
©
Baxi Heating U.K. Limited 2010.
INSTALLER GUIDE