flames should gradually become lower but remain alight. Depress the control knob
slightly to release from the ‘LOW’ position and turn back (clockwise) to the Pilot
ignition position. The main burner should extinguish but the pilot should remain alight.
Depress the control knob slightly and turn back (clockwise) to turn OFF.
This will extinguish the pilot.
10.2.3
Checking the inlet pressure.
The appliance is pre-set to give the correct heat
input at the inlet pressure shown in section 2 of this
manual. No adjustment is necessary.
1.
Check the inlet pressure by fitting a pressure
gauge at the test point. The test point is on the inlet
‘T’ connector (See figure 22). Check the pressure
with the appliance alight and set at maximum output.
2.
After checking, turn off the appliance. Remove the
pressure gauge and replace the test point sealing
screw.
3.
Test around the sealing screw for gas soundness
with a suitable leak detection fluid.
11. CERAMIC WALLS INSTALLATION
1.
Fit the ceramic rear wall inside the
“L” bracket on the back face of the
burner compartment. Push the
ceramic wall flat against the back face
of the burner compartment (See figure
23).
Page 26
©
Baxi Heating U.K. Limited 2010.
Figure 23. Ceramic rear wall installation
Figure 22. Pressure test point
INSTALLER GUIDE