If the smoke is drawn into the appliance, continue with the installation. If the test is
not satisfactory
disconnect the appliance and advise the customer of the cause
of failure
.
14.2 Flame supervision and spillage monitoring system.
The pilot unit incorporates a system that will automatically shut off the gas supply if
the pilot flame goes out or if there is insufficient oxygen due to spillage or lack of
ventilation.
Check that the system operates properly as follows:
Light the appliance. Set at the “HIGH” position and leave for one minute.
Turn back to “OFF” to extinguish the pilot.
Note the time when the pilot goes
out.
Listen for a snap sound at the gas tap.
Note the time when the sound is
heard.
An electromagnetic valve shutting off the gas supply through the tap causes
this sound. The valve is located in the body of the tap. The valve should operate
within 60 seconds of the pilot going out.
If the valve does not operate within this
time limit do not allow the appliance to be used until the fault has been corrected.
This monitoring system must not be adjusted, bypassed or put out of
operation.
This monitoring system, or any of its parts, must only be exchanged using
authorised parts.