background image

This will extinguish the pilot.

Inlet pressure check.

The appliance is pre-set to give the correct heat input at the inlet pressure shown in
section 2 of this manual. No adjustment is necessary. 

1.

Check the inlet pressure by fitting a pressure gauge at the test point. The test point

is on the inlet ‘T’ connector (See
figure 9). Check the pressure with
the appliance alight and set at
maximum output.

2.

After checking, turn off the

appliance. Remove the pressure
gauge and replace the test point
sealing screw.

3.

Relight the appliance. Turn to the

maximum output position and test
around the sealing screw for gas
soundness with a suitable leak
detection fluid.

Check for spillage.

1.

Close all doors and windows in the room containing the appliance.

2.

Light the appliance and turn the control knob to the ‘HIGH’ position.

3.

Leave the appliance on for five minutes.

4. 

A smoke match should be placed close to base of the diverter box. The installation

is satisfactory if the smoke is drawn into the appliance/ flue way. Do not use a lighted
match or a naked flame.
If the smoke is not drawn into the appliance leave the appliance alight at the
maximum setting for a further ten minutes and then repeat the test. If the flue
restrictor is fitted (See page 6 - point 4) then remove the restrictor and repeat the
above test. If the smoke is still not drawn into the appliance then 

disconnect the

appliance and seek expert advice.

5.

If the above test is satisfactory open all internal connecting doors, hatches, etc. in

the room. Keep all doors and windows that open to the outside of the building closed.
Recheck for spillage as above. If an extractor fan is installed in the same room as the
appliance or a connecting room, check that spillage does not occur with the fan
operating and all doors and other openings between the fan and the appliance open.
If the smoke is drawn into the appliance, continue with the installation. If the test is
not satisfactory 

disconnect the appliance and advise the customer of the cause

of failure

.

Flame supervision and spillage monitoring system.

The pilot unit incorporates a system that will automatically shut off the gas supply if
the pilot flame goes out. Check that the system operates properly as follows;

Page 13

INSTALLER GUIDE

© 

Baxi Heating U.K. Limited 2007.

Figure 9.

Summary of Contents for Firefox 5 910

Page 1: ...CONVERSION KIT NO 0591011 THIS APPLIANCE IS FOR USE WITH PROPANE GAS G31 THIS APPLIANCE IS SUITABLE ONLY FOR INSTALLATION IN THE UNITED KINGDOM GB AND THE REPUBLIC OF IRELAND IE Firefox 5 Model 910 CAST IRON GAS STOVE Fitted with a Ceramic Coal fuel effect GC No 32 264 24 For technical advice firstly contact your retailer If further advice is required then call 01204 868550 ...

Page 2: ...ils of the proposed use to the following address The Company Secretary Baxi Heating UK Limited The Wyvern Business Park Stanier Way Derby DE21 6BF Warning Any person who does any unauthorised act in relation to a copyright work may be liable to criminal prosecution and civil claims for damages Valor Fires Erdington Birmingham B24 9QP Because our policy is one of constant development and improvemen...

Page 3: ...evice be altered or bypassed in any way Only a genuine manufacturers replacement part should be fitted Before continuing any further with the installation of this appliance please read the following guide to manual handling The lifting weight of this appliance is 55 kg We therefore recommend that two people should be sufficient to lift the stove If fitting or moving the stove alone we recommend th...

Page 4: ... for energy rating of dwellings The conversion of net efficiency to gross was achieved by multiplying the net efficiency by the following conversion factor from Table E3 of SAP 2005 rounding down to the nearest whole number Gas Conversion factor from net to gross efficiency Natural Gas 0 901 LPG 0 921 Gas Natural G20 Propane G31 Inlet Pressure 20mbar 37mbar Input Max Gross 5 50kW 18 766Btu h 5 4kW...

Page 5: ...disposed at a landfill licensed to accept such waste Protective clothing is not required when handling these articles but we recommend you follow the normal hygiene rules of not smoking eating or drinking in the work area and always wash your hands before eating or drinking This appliance does not contain any component manufactured from asbestos or asbestos related products 3 UNPACKING Before inst...

Page 6: ...eet with holes in the base We recommend that these be placed at the rear of the stove 2 Place the front cover casting on top of the front legs 3 Secure the legs and front cover casting to the underside of the casting body using the bolts and washers supplied The bolts should have the locking washer added first followed by the flat washer 4 This appliance is supplied with a flue restrictor for use ...

Page 7: ...ront bolt and nut that secure the cast collar to the outside of the cast body Unscrew and remove the nut and washer from inside the top of the casting body Position the down draught diverter as in figure 3 It MUST be sealed against the top of the stove casting It is important that it sits on top and between the raised cast areas on the rear of the stove body See figure 3 Secure in place using the ...

Page 8: ... and washers supplied 8 Offer the burner module into the stove and connect the thermal switch leads to the tags mid way along the thermocouple 9 Locate the burner assembly inside the stove body as in figure 5 The outer front of the stove is not shown for clarity The rear leg of the burner should sit on the rear of the casting Secure using the three screws supplied The screw locations are shown ion...

Page 9: ...edition of the Building Standards Scotland Regulations issued by the Scottish Executive In Northern Ireland the current edition of the Building regulations Northern Ireland issued by the Department of the Environment for Northern Ireland In the republic of Ireland the installation must be carried out by a competent person and also conform to the relevant parts of a The current edition of IS 813 Do...

Page 10: ... flue outlet is correctly positioned to align with the flue outlet on the stove and that the chimney is in good condition If not a chimney liner must be installed or a suitable class 2 gas flue used A draught is necessary to ensure the products of combustion are fully evacuated Connect and seal the the stove flue collar to the chimney using full depth of collar The flue must have a minimum effecti...

Page 11: ...t not be installed unless the fan is permanently disconnected Location This appliance must not be installed in a private garage or any room which contains a bath or shower or where steam is regularly present Propane gas Propane gas appliances must not be installed in a cellar basement or other room which is built entirely below ground level See Gas Safety Installation and use Regulations Gas conne...

Page 12: ... Repeat this operation until a flame appears at the pilot The pilot can be seen by looking through the space in the left hand front of the fuel effect See figure 8 There may be a delay before the pilot lights due to air being purged from the system When a flame appears at the pilot keep the control knob depressed and hold the pilot ignition position for five seconds When the control knob is releas...

Page 13: ... flame If the smoke is not drawn into the appliance leave the appliance alight at the maximum setting for a further ten minutes and then repeat the test If the flue restrictor is fitted See page 6 point 4 then remove the restrictor and repeat the above test If the smoke is still not drawn into the appliance then disconnect the appliance and seek expert advice 5 If the above test is satisfactory op...

Page 14: ... ten minutes before relighting Stress that if the monitoring system repeatedly shuts off the stove the appliance should be switched off and a specialist should be consulted Advise the customer that they should read their owner guide before operating the stove and always follow the advice in the section headed Cleaning your stove Stress that no extra ceramic fuel effect pieces must be added over an...

Page 15: ...und the stove before and after working on the stove When replacing these articles we recommend that the replaced items are not broken up but are sealed within a heavy duty polythene bag clearly labelled as RCF waste RCF waste is classed as a stable non reactive hazardous waste and may be disposed at a landfill licensed to accept such waste Protective clothing is not required when handling these ar...

Page 16: ... to ensure that the aeration setting is correct Check the aeration shutter setting See figure 10 2 To adjust the aeration setting loosen the two aeration shutter screws slide the aeration shutter to the position shown in figure 9 and tighten the fixing screws Page 16 INSTALLER GUIDE Baxi Heating U K Limited 2007 Figure 10 Aeration shutter setting ...

Reviews: