INSTRUCTIONS FOR FITTERS
21. PARAMETERS SETTING
To set the boiler parameters, proceed as follows:
• press the key
IP
for at least three seconds ;
• press and hold down the key
and then press
(see figure at side). When the function
is active, the letters “F01” and the value of the selected parameter appear on the display.
Changing the parameters
•
Press the
+/-
buttons to scroll through the parameters;
•
Press the
+/-
buttons to change each parameter value;
NOTE:
the value is automatically memorised after about 3 seconds. (Do not press any key until the value starts to flash).
0607_1908
Factory settings
Description of parameters
140 Fi 240 Fi
280 Fi 320 Fi
240 i
280 i
F01
Type of boiler
10
= sealed chamber -
20
= atmospheric chamber
10
20
F02
Gas used
00
=
NATURAL (METHANE) - 01 = LPG
00 or 01
F03
Hydraulic system
06
F04
Setting programmable relays 1
02
= zone system (See SERVICE Instructions)
02
F05
Setting programmable relays 2
13
= “cool” function for external conditioning system
04
(See SERVICE Instructions)
F06
Configuration of external probe inlet
(See SERVICE Instructions)
00
F07…F09
Manufacturer’s information
00
Mode of installing the climate controller
F10
00
= on the wall (paragraph 18.2)
00
01
= Not used
02
= in the boiler (paragraph 18.1)
F11…F12
Manufacturer’s information
00
F13
Max heating power
(0-100%)
100
F14
Max DHW power
(0-100%)
100
F15
Min heating power
(0-100%)
00
F16
Setting of maximum heating setpoint (°C)
00
= 85°C -
01
= 45°C
00
F17
Pump post-circulation time in heating (01-240 minutes
)
03
F18
Waiting time in heating before a new ignition
(00-10 minutes) - 00=10 seconds
03
F19
Manufacturer’s information
07
F20
Manufacturer’s information
00
F21
Anti-legionella function
00
= Disabled
-
01
= Enabled
00
F22
Manufacturer’s information
00
F23
Maximum DHE setpoint temperature (ACS)
65
F24
Manufacturer’s information
35
F25
Protection device against water lack
01
F26…F29
Manufacturer’s information (read-only parameters)
--
F30
Manufacturer’s information
10
F31
Manufacturer’s information
00
F32…F41
Diagnostics (See SERVICE Instructions)
--
last
Activation of calibration function
0
parameter
(See SERVICE Instructions)
ATTENTION: do not change the value of the “Manufacturer’s information” parameters
.