Fig. 43: charging control /schematically)
ON / OFF
Collector pump
Tkol
Collector
temp
TLmin
Charging temp min buffer / swimming pool
TSp
Storage
temperature
Charg temp min DHW st tank
(3812)
In addition to the temperature difference, reaching a certain collector tempera-
ture is necessary for the storage charging process.
Fig. 44: Charging controller (dT)
Tcol
On/Off
SdON
SdOFF
Collector temperature
Charging ON / OFF
Temp diff ON
Temp diff OFF
Temp diff ON buffer
(3813)
Temp diff OFF buffer
(3814)
Charging temp min buffer
(3815)
The switching-on and switching-off point of the collector pump is set with these
functions. Basis is the temperature difference between collector temperature and
storage temperature of the buffer.
In addition to the temperature difference, reaching a certain minimum collector
temperature is necessary for the buffer storage charging process.
Temp diff ON swi pool
(3816)
Temp diff OFF swi pool
(3817)
For exceeding or not reaching the difference between solar collector temperature
and swimming pool temperature, the solar pump is switched on and off.
Programming
4
1
1
Summary of Contents for POWER HT-A 1.430
Page 1: ... 1 QVWDOODWLRQ PDQXDO DV FRQGHQVLQJ ERLOHUV 3RZHU 7 ...
Page 8: ......
Page 13: ...3 4 Wiring diagram Fig 3 Wiring diagram Technical Data 3 1 ...
Page 41: ...Connection diagram Prior to installation 1 4 ...
Page 43: ...Connection diagram Prior to installation 3 4 ...
Page 45: ...Connection diagram Prior to installation 5 4 ...
Page 47: ...Wiring plan right POWER HT A Prior to installation 47 ...
Page 48: ...Wiring plan left POWER HT A Prior to installation 48 ...
Page 49: ...4 17 Legend Prior to installation 9 4 ...
Page 161: ...Space for notes 1 6 1 ...
Page 162: ...Space for notes 2 6 1 ...
Page 163: ...Space for notes 3 6 1 ...
Page 164: ......