Fig. 48: Example for heat demand 10 V and cooling demand 10 V
s
3
x
F1
Function value 1
F2
Function value 2
U1
Voltage value 1
U2
Voltage value 2
PWM-output P1
(6085)
With this parameter the function for the modulating pumps is specified.
-
None
: No output P1 exists.
-
Boiler pump Q1
: the connected pump is used for recirculation of the boiler wa-
ter.
-
DHW pump Q3
: Control element for drinking water storage.
-
DHW interm circ pump Q33
: Charge pump for domestic hot water storage with
external heat exchanger.
-
Heat circuit pump HC1 Q2
: the heat circuit pump HC1 will be activated.
-
Heating circuit pump HC2 Q6
: the heat circuit pump HC2 will be activated.
-
Heating circuit pump HC3 Q20
:the heat circuit pump HC3 will be activated.
-
Collector pump Q5
: a circulation pump for the collector circuit is required for
connection of a solar collector.
-
Solar pump ext exch K9
: if several exchangers are connected, the buffer storage
must be set at the respective relay output. and the type of the solar regulating
unit must be defined in prog.no. 5840.
-
Solar pump swi pool K18
: if several exchangers are connected, the the swim-
ming pool must be set at the respective relay output. and the type of the solar
regulating unit must be defined in prog.no. 5840.
Sensor type collector
(6097)
Selection of used sensor types for measurement of the collector temperature.
Readjustm coll sensor 1
(6098)
Setting a correction value for collector sensor 1.
Readjustm outside sensor
(6100)
Setting a correction value for outside sensor.
Time constant building
(6110)
The value set here influences the reaction speed of the nominal flow value in case
of fluctuating outside temperatures as a function of the building design.
possible values (see also
Quick setback
prog.-no. 780, ... ):
- 40 for buildings with thick walls or outer insulation.
- 20 For buildings of normal building design.
- 10 For buildings of light building design.
Programming
9
2
1
Summary of Contents for POWER HT-A 1.430
Page 1: ... 1 QVWDOODWLRQ PDQXDO DV FRQGHQVLQJ ERLOHUV 3RZHU 7 ...
Page 8: ......
Page 13: ...3 4 Wiring diagram Fig 3 Wiring diagram Technical Data 3 1 ...
Page 41: ...Connection diagram Prior to installation 1 4 ...
Page 43: ...Connection diagram Prior to installation 3 4 ...
Page 45: ...Connection diagram Prior to installation 5 4 ...
Page 47: ...Wiring plan right POWER HT A Prior to installation 47 ...
Page 48: ...Wiring plan left POWER HT A Prior to installation 48 ...
Page 49: ...4 17 Legend Prior to installation 9 4 ...
Page 161: ...Space for notes 1 6 1 ...
Page 162: ...Space for notes 2 6 1 ...
Page 163: ...Space for notes 3 6 1 ...
Page 164: ......