10.0
Installation of solar controller
Collector
Type 0:
1 collector, 1 storage tank
Tcoll
Tret
FM
P
Storage tank
Tth
Tst
Collector
Type 2:
1 collector, 2 storage tanks
with 2 pumps
Tcoll
Tret
FM
P1
Storage tank1
Storage tank2
Tth
Tst1
Tst2
P2
Collector 1
Type 4:
2 collectors, 1 storage tank
with 2 pumps
Tcoll1
Tcoll2
P1
P2
Tret
FM
Storage tank1
Tth
Tst
System type
Sensor terminal designation (see Fig. 25)
Type
Description
T1
T2
T3
T4
T5
T6
0
1 collector array, 1 storage cylinder
Tcoll1
Tst1
-
Tret
Tth
2
1 collector array, 2 storage cylinder (pump-pump)
Tcoll1
Tst1
Tst2
Tret
Tth
4
2 collector array, 1 storage cylinder (pump-pump)
Tcoll1
Tst1
Tcoll2
Tret
Tth
NOTE:The solar gain flowmeter must be connected to sensor terminals marked WMM (see Fig. 25).
System type
Output terminal designation (see Fig. 25)
Type
Description
A1
A2
A3
0
1 collector array, 1 storage cylinder
P1
-
Auxiliary heating
2
1 collector array, 2 storage cylinder (pump-pump)
P1
P2
4
2 collector array, 1 storage cylinder (pump-pump)
P1
P2
Fig. 27
10.6
Solar Gain measurement
For solar gain measurement it is necessary to fit the
flowmeter and collector return sensor (Tret) as shown in the
diagram in Fig. 27.The collector return sensor must be
securely attached to the return pipework using the securing
ties supplied and then covered by insulation.The solar gain of
the system is calculated on the basis of the temperature
difference between the collector flow and return and the
solar primary circulation flow rate.
The function must be switched “on”
when commissioning
the Solar Controller. Refer to the Solarflo
TM
“Commissioning,
Maintenance & Servicing Guide” for further details.
For System Types 2 and 4 the additional pump (P2) can be
ordered as an accessory, Part No. 5129362
Tcoll
Temperature measuring point collector
Tth
Temperature measuring point thermostat auxiliary
sensor
Tret
Temperature measuring point collector return
Tst
Temperature measuring point storage tank
P
Pump
FM
Flowmeter