5.0 Installation
20
5.8
Left or Right Flue
Concentric flue kits are available to allow 3
metres horizontal and 4 metres vertical
flueing. Twin flue at 80mm diameter will allow
up to 15 metres vertical flueing.
NOTE:
If the flue terminal is inaccessible from
outside the building, it is necessary to fix the
internal fitting kit in position before continuing
with the installation. (See section 5.15 Internal
Fitting Kit of these instructions).
1. The procedure for fitting the appliance flued to
the left or right hand side is the same.
2.
30-40-50 PF
- Left/Right Hand Side maximum
flue 410mm (16 in).
3.
60-70-80 PF
- Left/Right Hand Side maximum
flue 355mm (14 in).
4. Using the previously marked flue hole centre
(Section 5.3) and the two marks made at the
triangular cutouts of the template, mark the
horizontal centre line for the flue assembly
(Fig. 34).
5. Extend this line either left or right as required,
to the corner of the room (Fig. 34).
6. Extend the horizontal centre line around the
corner for approximately 300mm (12 in). Ensure
that the line remains horizontal by checking with a
spirit level (Fig. 35).
7. From the wall template cut out the ‘D’ shaped
section. Using this as a template, line up the
horizontal triangular cut outs with the extended
300mm (12 in) line and make sure that the flat of
the template is butted up against the corner of the
wall (Fig. 36).
8. If the appliance mounting wall is out of true, use
string or a straight edge to determine the true
corner position and mark a vertical line to
accommodate the flat edge of the template.
9. Holding the template firmly, mark the vertical
centre line for the flue assembly by marking the
point at the outer corners of the upper and lower
cut outs (Fig. 37).
10. Remove the template and draw a vertical line
between the two marks. The intersection of the
vertical and horizontal lines is the centre of the
flue hole (Fig. 38).
11. If using the internal fitting kit a 117mm (4
5
/
8
in)
diameter hole is required.
12. Cut a hole approximately 107mm (4
1
/
4
in)
diameter in the masonry for the 100mm (4 in)
diameter flue duct (Fig. 39). (Use of a core drill is
recommended. When using a core drill, it is
important to keep the drill level and square,
particularly with the wall onto which the boiler is to
be fitted).
13. Drill the anchorage holes 63mm (2
1
/
2
in) deep
to accept suitable wall plugs.
Fig. 34
Fig. 35
Fig. 36
Fig. 37
Fig. 38
Fig. 39
Maximum lengths for side flues using the standard telescopic flue kit
410mm (30, 40, 50)
410mm (30, 40, 50)
355mm (60, 70, 80)
355mm (60, 70, 80)
Summary of Contents for Solo 3 30 PF
Page 45: ...13 0 Notes 45 ...
Page 46: ...13 0 Notes 46 ...