Fig.20
Noise abatement screen
MW-C000373-1
Brrrrr....
Brrrrr....
Br
rrr
r...
.
Brrrrr....
Locate the noise abatement screen as close as possible to the noise
source whilst allowing for the free circulation of air in the exchanger on the
outdoor unit and maintenance work.
Fig.21
Distances of the appliance from the wall
MW-5000579-1
E
E
D
D
A
A
B
B
A
A
A
C
C
Max.
500
Max.
500
Tab.15 Minimum dimensions in mm
SPC SPLIT
A
300
B
1500
C
500
D
200
E
600
Installation in cold and snowy regions
Wind and snow may significantly impair the performance of the heat
pump. Ensure that the following information is respected to install the
outdoor unit correctly.
Always install the outdoor unit sufficiently high off the ground to allow
correct condensates discharge.
The width of the base must not exceed the width of the outdoor unit.
Icing may lead to it breaking (refrigerant fluid leak).
5 Before installation
36
SPC Split
7740321 - v04 - 03122019