11.2 Running diagnostics on errors on the outdoor unit
To run diagnostics on certain errors shown by the control panel, it may be
necessary to refer to the parameters directly on the outdoor unit.
Important
Only qualified persons may carry out diagnostics of the outdoor
unit as the process is carried out directly on the outdoor unit.
1. Switch the thermodynamic water heater off.
2. Remove the top panel on the outdoor unit.
3. Switch the thermodynamic water heater back on.
Danger
Electrified bare parts are then accessible.
4. Scroll through the parameters by pressing the QUERY button.
See
Outdoor unit list of parameters.
5. Once diagnostics are complete, refit the top panel on the outdoor unit.
11.2.1 Outdoor unit list of parameters
Tab.30 Outdoor unit parameters
Parameter No.
Description of the parameter
Values displayed
0
Normal display
Water temperature T5L
dF : Defrosting phase
dC : Refrigerant fluid recovery mode
0: Holiday mode
1
Mode
2: In residence
8: Holiday
2
Fan speed
F0: Shut-down
F1: Low speed
F2: High speed
3
Evaporation temperature (T3)
4
Air temperature (T4)
5
Water temperature (T5L)
6
Intake temperature (Th)
7
Discharge temperature (Tp)
8
Electrical current required:
to the electrical back-up,
to the compressor
9
Degree to which the electronic pressure release
valve is open
Open = value displayed x 8
10
Setpoint temperature (Ts)
11
Trip temperature of the electrical back-up (Td)
12
Hysteresis (Tr)
13
Last error code
14
Software version
15
End of parameters
“__”
Fig.74
MW-4000189-2
2
4