background image

  The MC55 function provides an interlock ratchet of Relay 1 and 

Relay 2 triggered by Inputs 1 and 2, with door position switch 

inputs on Input 3 for Input 1 and Input 4 for Input 2.  Only one 

relay will be allowed to operate at a time thus making the two 

relays interlocked or mutually exclusive.  In order to activate a 

relay, its corresponding position switch input must be closed. 

Each trigger of an input will change the state of its respective 

relay.  MC55 has NO adjustable parameters.  If the input is 

maintained, its relay will only change state once.  The input must 

then be opened and re-closed for a change of state.

NOTE:  The door position switch must have a closed 

contact when the door is closed and an opened 

contact when it is not.

A typical application is to have a pair of doors on a clean room in 

which only one door can be opened at a time.  Each door would 

have a set of push-plates connected to it in the instance that a 

single hold time will not suit all users of the door.  Each door would 

also have a door position switch.  For this scenario door number 

1 and 2 push plates shall be wired in parallel to inputs 1 and 2 

respectively, with the door position switches wired to Input 3 and 

Input 4 respectively, door controller 1 would be wired to Relay 

1 and door controller 2 would be wired to Relay 2.  An example 

wiring diagram for this scenario is shown below.

MC55 SETUP

1.  Wire the Br3 accordingly.

2.  Select the MC55 as the function according to the steps outlined in Section 5 – Selecting the Function.

•  Press and hold both push buttons (INCR & PARAM) for three (3) seconds to activate the display.

•  Press the INCR button to toggle through each function and select 

55

.

3.  There are NO parameters to set for the MC55 as the state of Relay 1 and Relay 2 are not based on time, so just wait for the display to 

become inactive to save the configuration. 

4.  Once programming is complete, test the Br3.   Wait until both doors are closed then trigger Relay 1 via Input 1.  Ensure that Relay 1 changes 

state and that is maintained.  The display will show 

R1

 when Relay 1 is energized.   Test the interlock by attempting to trigger Relay 2 via 

Input 2.  Relay 2 should NOT activate due to the first position switch being opened.  Now trigger Relay 1 again via Input 1 and ensure Relay 

1 changes state again.   The display will show 

55

 when Relay 1 is de-energized.  Once the first position switch is closed trigger Relay 2 via 

Input 2.  Ensure that Relay 2 changes state and that is maintained.  The display will show 

R2

 when Relay 2 is energized.  Test the interlock 

by attempting to trigger Relay 1 via Input 1.  Relay 1 should NOT activate due to the second position switch being opened.  Now trigger Relay 

2 again via Input 2 and ensure Relay 2 changes state again.   The display will show 

55

 when Relay 2 is de-energized.

5.  Upon completion of the above steps, walk test the door to ensure all functions, timers, sensors, etc. are working as intended, and that the 

system is in compliance with all applicable standards (i.e. ANSI A156.10, A156.19).

6J   Function 

55

 - Interlock Ratchet (MC55)

75.5501.02  EN   20091102   (75.5500)   

 

 

 

 

 

 

 

 

Page 12 of 15

G

N

D

IN

-1

G

N

D

IN

-2

G

N

D

IN

-3

G

N

D

IN

-4

1

2

3

4

WET

WET

WET

N

C

N

O

C

O

M

N

C

N

O

C

O

M

12

-2

4V

AC

/D

C

RELAYS

1

2

POWER

RELAY 1

IN

C

R

.

PARAM

SETUP

D

C

AC

D

R

Y

W

ET

INPUTS

5 5

N

C

N

O

C

O

M

3

Br

3

CAUTION:  RELAY 1 WET 

OUTPUT OPTION 

IS ACTIVE FOR 

ALL FUNCTIONS.

12 to 24

 VAC/VDC

+/- 10%

Directly to Activation Circuit of

Door Control #1 and Door Control

Activation Circuit of Door #2.

Inputs 1 & 2 are activation

inputs for Doors 1 & 2.

Inputs 3 & 4 are for the door position switch for inputs

1 & 2 respectively.  Switch is closed when door is closed.

Summary of Contents for Br3

Page 1: ...n switch input for which closing it will re inhibit Input 1 Simply put this function is a combination between a LE21 and MC25 6 2 5 MC25 2 Relay Sequence Provides a sequence for Relay 1 and or Relay 2 triggered by Input 1 or WET Input 7 2 8 MC28 2 Relay Sequence w Door Position Input Provides a sequence for Relay 1 and or Relay 2 triggered by Input 1 or WET Input Additionally Input 2 provides a do...

Page 2: ...IPTION SPECIFICATION Supply Voltage 12 to 24 VAC VDC 10 Contact Rating DRY Relay 1 Relay 2 Relay 3 Contact Rating WET Relay 1 3 A at 24 VAC 3 A at 30 VDC 3 A at 24 VAC 3 A at 30 VDC 1 A at 24 VAC 1 A at 30 VDC 1 A Current Consumption 30 to 130 mA DRY Output Temperature Range 15 F 26 C to 150 F 65 C Dimensions 5 2 133mm W x 2 2 55mm D x 1 25mm H Input Specification Inputs 1 to 4 DRY Contact WET Inp...

Page 3: ...long as no relays are active the display will show the function selected otherwise it will show those relays Once the values are changed they are only saved after the display goes inactive again 5 seconds NOTE Remember that the INCR push button always increments the value of the parameter that you are looking at and the PARAM push button toggles through the available parameters NOTE To change only...

Page 4: ...system is in compliance with all applicable standards i e ANSI A156 10 A156 19 75 5501 02 EN 20091102 75 5500 Page 4 of 15 6A Function 10 Timer Module MC10 GND IN 1 GND IN 2 GND IN 3 GND IN 4 1 2 3 4 WET WET WET NC NO COM NC NO COM 12 24V AC DC RELAYS 1 2 POWER RELAY 1 INCR PARAM SETUP DC AC DRY WET INPUTS 1 0 NC NO COM 3 Br3 CAUTION RELAY 1 WET OUTPUT OPTION IS ACTIVE FOR ALL FUNCTIONS 12 to 24 V...

Page 5: ...le parameter for the LE21 function is shown in the chart Set it as needed for the application and wait for the display to become inactive to save the configuration PARAMETER PARAM Button DESCRIPTION POSSIBLE VALUES INCR Button H1 Relay 1 hold time 00 through 60 Relay 1 hold time will not begin counting down until the release of an activation input 4 Once programming is complete test the Br3 Attemp...

Page 6: ...M button to cycle through and set the parameters Press the INCR button to increment the parameter s value Parameters for the LE22 function are shown in the chart Set the parameters as needed for the application and wait for the display to become inactive to save the configuration PARAMETER PARAM Button DESCRIPTION POSSIBLE VALUES INCR Button H1 Relay 1 hold time 00 through 60 Relay 1 hold time wil...

Page 7: ...ding to the steps outlined in Section 5 Selecting the Function Press PARAM button to cycle through and set the parameters Press the INCR button to increment the parameter s value Parameters for the MC25 function are shown in the chart Set the parameters as needed for the application and wait for the display to become inactive to save the configuration PARAMETER PARAM Button DESCRIPTION POSSIBLE VA...

Page 8: ...ers Press the INCR button to increment the parameter s value Parameters for the MC28 function are shown in the chart Set the parameters as needed for the application and wait for the display to become inactive to save the configuration PARAMETER PARAM Button DESCRIPTION POSSIBLE VALUES INCR Button H1 Relay 1 hold time 00 through 60 Relay 1 hold time will not begin counting down until the release o...

Page 9: ...METER PARAM Button DESCRIPTION POSSIBLE VALUES INCR Button H1 Relay 1 hold time 00 through 60 Relay 1 hold time will not begin counting down until the release of Input 2 H2 Relay 2 hold time 00 through 60 Relay 2 hold time will not begin counting down until the delay between Relay 1 and Relay 2 expires D1 Delay between Relay 1 and Relay 2 00 _1 1 4 _2 1 2 _3 3 4 01 through 60 seconds The delay tim...

Page 10: ... application it will still function as Input 1 does if used MC35 SETUP 1 Wire the Br3 accordingly 2 Select the MC35 as the function according to the steps outlined in Section 5 Selecting the Function Press and hold both push buttons INCR PARAM for three 3 seconds to activate the display Press the INCR button to toggle through each function and select 35 3 Set the MC35 parameters according to the s...

Page 11: ...ay to become inactive to save the configuration PARAMETER PARAM Button DESCRIPTION POSSIBLE VALUES INCR Button H1 Relay 1 hold time 00 through 60 Relay 1 hold time will not begin counting down until the release of Input 1 H2 Relay 2 hold time 00 through 60 Relay 2 hold time will not begin counting down until the release of Input 2 4 Once programming is complete test the Br3 Wait until both doors a...

Page 12: ...set for the MC55 as the state of Relay 1 and Relay 2 are not based on time so just wait for the display to become inactive to save the configuration 4 Once programming is complete test the Br3 Wait until both doors are closed then trigger Relay 1 via Input 1 Ensure that Relay 1 changes state and that is maintained The display will show R1 when Relay 1 is energized Test the interlock by attempting ...

Page 13: ...n to increment the parameter s value Parameters for the MC65 function are shown in the chart Set the parameters as needed for the application and wait for the display to become inactive to save the configuration PARAMETER PARAM Button DESCRIPTION POSSIBLE VALUES INCR Button H1 Relay 1 hold time 00 through 60 Relay 1 hold time will not begin counting down until the release of Input 1 for inbound or...

Page 14: ...e Function Press PARAM button to cycle through and set the parameters Press the INCR button to increment the parameter s value Parameters for the MC75 function are shown in the chart Set the parameters as needed for the application and wait for the display to become inactive to save the configuration PARAMETER PARAM Button DESCRIPTION POSSIBLE VALUES INCR Button H1 Relay 1 hold time 00 through 60 ...

Page 15: ...programmed 3 Jumper an active Input and ensure that the fault is not within the wiring If module works when jumped trace wiring from Inputs relays 4 Replace module Module reacts to input but has no output 1 Wrong outputs are connected 2 Incorrect wiring 3 Incorrect jumper settings 4 Faulty module 1 Check to ensure that the proper outputs are connected per the function selected 2 Trace all wiring t...

Reviews: