background image

  The MC65 function provides a two-way sequencer to sequence 

Relay 1 and/or Relay 2 triggered by Input 1.  Similarly, it also 

provides a sequence in the opposite direction to sequence 

Relay 2 and/or Relay 1 triggered by Input 2.  Inputs 3 and 4 also 

trigger Relays 1 and 2 individually (non-sequenced).  Adjustable 

parameters include 

H1

 for activation hold time of Relay 1, 

H2

 for 

activation hold time of Relay 2, 

D1

 for delay between activation 

of Relay 1 to Relay 2 and 

D2

 for delay between activation of 

Relay 2 to Relay 1.  A re-activation of Input 1 or Input 2 before 

the sequence expires will re-start both hold timers and keep the 

relays active.  A maintained input will freeze both hold timers, 

thus keeping their relays active until the input is released, which 

will allow the hold timers to expire and deactivate the relays 

normally.

  

NOTE

:  The delay timer will only fire one time during initial 

activation or maintained input.

NOTE:  The functionality for MC65 has changed slightly in this 

version as you no longer have to wait for a sequence to 

complete before running another sequence.

A typical application is an unsecured two door sequence vestibule 

that allows two-way traffic in which you have a push-plate on the 

entrance of each door to start the sequence and two push-plates 

between the doors to activate the doors individually in case of 

entrapment.  For this scenario the push-plate for in-bound traffic 

would be wired to Input 1, the push-plate for out-bound traffic 

would be wired to Input 2, a push-plate for entrapment release 

of door 1 would be wired to Input 3, a push-plate for entrapment 

release of door 2 would be wired to Input 4, Relay 1 would be 

wired to door controller 1 and Relay 2 would be wired to door 

controller 2.  An example wiring diagram for this scenario is shown.

MC65 SETUP

1.  Wire the Br3 accordingly.

2.  Select the MC65 as the function according to the steps outlined in Section 5 – Selecting the Function.

•  Press and hold both push buttons (INCR & PARAM) for three (3) seconds to activate the display.

•  Press the INCR button to toggle through each function and select 

65

.

3.  Set the MC65 parameters according to the steps outlined in Section 5 – Selecting the Function.  

•  Press PARAM button to cycle through and set the parameters.

•  Press the INCR button to increment the parameter’s value.

Parameters for the MC65 function are shown in the chart.  Set the parameters as needed for the application, and wait for the display to 

become inactive to save the configuration.

PARAMETER

(PARAM Button)

DESCRIPTION

POSSIBLE VALUES

     (INCR Button)

H1

Relay 1 hold time

00

’ through ‘

60

’ - Relay 1 hold time will not begin counting down until the release of Input 1 

for inbound or until the delay between Relay 2 and Relay 1 expires for outbound or until 

the release of Input 3.

H2

Relay 2 hold time

00

’ through ‘

60

’ - Relay 2 hold time will not begin counting down until the release of Input 2 

for outbound or until the delay between Relay 1 and Relay 2 expires for 

inbound or until the release of Input 4.

D1

Delay between 

Relay 1 and Relay 2

00

’, ‘_

1

’ (1/4), ‘_

2

’ (1/2), ‘_

3

’ (3/4), ‘

01

’ through ‘

60

’ seconds. The delay time will begin 

counting down with the activation of the sequence.

D2

Delay between 

Relay 2 and Relay 1

00

’, ‘_

1

’ (1/4), ‘_

2

’ (1/2), ‘_

3

’ (3/4), ‘

01

’ through ‘

60

’ seconds. The delay time will begin 

counting down with the activation of the sequence.

4.  Once programming is complete, test the Br3.   Trigger the sequence via Input 1.  Ensure that the in-bound sequence runs and the relays 

activate and the timers are as programmed.  The display will show 

R1

 when Relay 1 is energized, 

R2

 when Relay 2 is energized and 

R=

 when 

both Relay 1 and Relay 2 are energized at the same time.   Trigger the sequence via Input 2.  Ensure that the out-bound sequence runs and 

the relays activate and the timers are as programmed.  Trigger only door 1 via Input 3.  Trigger only door 2 via Input 4.

5.  Upon completion of the above steps, walk test the door to ensure all functions, timers, sensors, etc. are working as intended and that the 

system is in compliance with all applicable standards (i.e. ANSI A156.10, A156.19).

6K   Function 

65

 - 2 Way, 2 Relay Sequence (MC65)

Page 13 of 15 

 

 

 

 

 

 

 

 

 

75.5501.02  EN   20091102   (75.5500)

G

N

D

IN

-1

G

N

D

IN

-2

G

N

D

IN

-3

G

N

D

IN

-4

1

2

3

4

WET

WET

WET

N

C

N

O

C

O

M

N

C

N

O

C

O

M

12

-2

4V

AC

/D

C

RELAYS

1

2

POWER

RELAY 1

IN

C

R

.

PARAM

SETUP

D

C

AC

D

R

Y

W

ET

INPUTS

6 5

N

C

N

O

C

O

M

3

Br

3

CAUTION:  RELAY 1 WET 

OUTPUT OPTION 

IS ACTIVE FOR 

ALL FUNCTIONS.

12 to 24

 VAC/VDC

+/- 10%

Directly to Activation Circuit of

Door Control #1 and Door Control

Activation Circuit of Door #2.

Input 4 allows Activation of Door #2 with NO Sequence to Door #1.

Input 3 allows Activation of Door #1 with NO Sequence to Door #2.

Input 2 allows Sequenced Activation from Door #2 to Door #1.

Input 1 allows Sequenced Activation from Door #1 to Door #2.

Summary of Contents for Br3

Page 1: ...n switch input for which closing it will re inhibit Input 1 Simply put this function is a combination between a LE21 and MC25 6 2 5 MC25 2 Relay Sequence Provides a sequence for Relay 1 and or Relay 2 triggered by Input 1 or WET Input 7 2 8 MC28 2 Relay Sequence w Door Position Input Provides a sequence for Relay 1 and or Relay 2 triggered by Input 1 or WET Input Additionally Input 2 provides a do...

Page 2: ...IPTION SPECIFICATION Supply Voltage 12 to 24 VAC VDC 10 Contact Rating DRY Relay 1 Relay 2 Relay 3 Contact Rating WET Relay 1 3 A at 24 VAC 3 A at 30 VDC 3 A at 24 VAC 3 A at 30 VDC 1 A at 24 VAC 1 A at 30 VDC 1 A Current Consumption 30 to 130 mA DRY Output Temperature Range 15 F 26 C to 150 F 65 C Dimensions 5 2 133mm W x 2 2 55mm D x 1 25mm H Input Specification Inputs 1 to 4 DRY Contact WET Inp...

Page 3: ...long as no relays are active the display will show the function selected otherwise it will show those relays Once the values are changed they are only saved after the display goes inactive again 5 seconds NOTE Remember that the INCR push button always increments the value of the parameter that you are looking at and the PARAM push button toggles through the available parameters NOTE To change only...

Page 4: ...system is in compliance with all applicable standards i e ANSI A156 10 A156 19 75 5501 02 EN 20091102 75 5500 Page 4 of 15 6A Function 10 Timer Module MC10 GND IN 1 GND IN 2 GND IN 3 GND IN 4 1 2 3 4 WET WET WET NC NO COM NC NO COM 12 24V AC DC RELAYS 1 2 POWER RELAY 1 INCR PARAM SETUP DC AC DRY WET INPUTS 1 0 NC NO COM 3 Br3 CAUTION RELAY 1 WET OUTPUT OPTION IS ACTIVE FOR ALL FUNCTIONS 12 to 24 V...

Page 5: ...le parameter for the LE21 function is shown in the chart Set it as needed for the application and wait for the display to become inactive to save the configuration PARAMETER PARAM Button DESCRIPTION POSSIBLE VALUES INCR Button H1 Relay 1 hold time 00 through 60 Relay 1 hold time will not begin counting down until the release of an activation input 4 Once programming is complete test the Br3 Attemp...

Page 6: ...M button to cycle through and set the parameters Press the INCR button to increment the parameter s value Parameters for the LE22 function are shown in the chart Set the parameters as needed for the application and wait for the display to become inactive to save the configuration PARAMETER PARAM Button DESCRIPTION POSSIBLE VALUES INCR Button H1 Relay 1 hold time 00 through 60 Relay 1 hold time wil...

Page 7: ...ding to the steps outlined in Section 5 Selecting the Function Press PARAM button to cycle through and set the parameters Press the INCR button to increment the parameter s value Parameters for the MC25 function are shown in the chart Set the parameters as needed for the application and wait for the display to become inactive to save the configuration PARAMETER PARAM Button DESCRIPTION POSSIBLE VA...

Page 8: ...ers Press the INCR button to increment the parameter s value Parameters for the MC28 function are shown in the chart Set the parameters as needed for the application and wait for the display to become inactive to save the configuration PARAMETER PARAM Button DESCRIPTION POSSIBLE VALUES INCR Button H1 Relay 1 hold time 00 through 60 Relay 1 hold time will not begin counting down until the release o...

Page 9: ...METER PARAM Button DESCRIPTION POSSIBLE VALUES INCR Button H1 Relay 1 hold time 00 through 60 Relay 1 hold time will not begin counting down until the release of Input 2 H2 Relay 2 hold time 00 through 60 Relay 2 hold time will not begin counting down until the delay between Relay 1 and Relay 2 expires D1 Delay between Relay 1 and Relay 2 00 _1 1 4 _2 1 2 _3 3 4 01 through 60 seconds The delay tim...

Page 10: ... application it will still function as Input 1 does if used MC35 SETUP 1 Wire the Br3 accordingly 2 Select the MC35 as the function according to the steps outlined in Section 5 Selecting the Function Press and hold both push buttons INCR PARAM for three 3 seconds to activate the display Press the INCR button to toggle through each function and select 35 3 Set the MC35 parameters according to the s...

Page 11: ...ay to become inactive to save the configuration PARAMETER PARAM Button DESCRIPTION POSSIBLE VALUES INCR Button H1 Relay 1 hold time 00 through 60 Relay 1 hold time will not begin counting down until the release of Input 1 H2 Relay 2 hold time 00 through 60 Relay 2 hold time will not begin counting down until the release of Input 2 4 Once programming is complete test the Br3 Wait until both doors a...

Page 12: ...set for the MC55 as the state of Relay 1 and Relay 2 are not based on time so just wait for the display to become inactive to save the configuration 4 Once programming is complete test the Br3 Wait until both doors are closed then trigger Relay 1 via Input 1 Ensure that Relay 1 changes state and that is maintained The display will show R1 when Relay 1 is energized Test the interlock by attempting ...

Page 13: ...n to increment the parameter s value Parameters for the MC65 function are shown in the chart Set the parameters as needed for the application and wait for the display to become inactive to save the configuration PARAMETER PARAM Button DESCRIPTION POSSIBLE VALUES INCR Button H1 Relay 1 hold time 00 through 60 Relay 1 hold time will not begin counting down until the release of Input 1 for inbound or...

Page 14: ...e Function Press PARAM button to cycle through and set the parameters Press the INCR button to increment the parameter s value Parameters for the MC75 function are shown in the chart Set the parameters as needed for the application and wait for the display to become inactive to save the configuration PARAMETER PARAM Button DESCRIPTION POSSIBLE VALUES INCR Button H1 Relay 1 hold time 00 through 60 ...

Page 15: ...programmed 3 Jumper an active Input and ensure that the fault is not within the wiring If module works when jumped trace wiring from Inputs relays 4 Replace module Module reacts to input but has no output 1 Wrong outputs are connected 2 Incorrect wiring 3 Incorrect jumper settings 4 Faulty module 1 Check to ensure that the proper outputs are connected per the function selected 2 Trace all wiring t...

Reviews: