TROUBLESHOOTING

Red LED does not 
illuminate during 
“closing” cycle 

OR

 red 

LED illuminates in latch 
check

Red and black wires are reversed 
(polarity sensitive)

Reverse the polarity of the moror wires.

AC motor application:  in-line 
resistor not installed

Install in-line resistor on red wire of LO-21 
(AC motors only).

Faulty input power or data

Check voltage supply to LO-21  
(12 – 24 VAC / 15 – 24 VDC).

Check voltage on orange, brown, red, and 
black wires.

Door will not open or 
close (green LED is on)

Lockout safety beams are blocked

1.  Remove any obstructions with safety 

beam path.

2.  Check all wiring related to safety 

beams.

3.  Test the safety beams for proper 

operation.

Faulty safety beam receiver or 
transmitter

Faulty power supply to safety 
beam

Faulty safety beam wiring

Door will not re-cycle 
open when activated 
during “closing” cycle

Lockout time is not long enough 
(red LED goes out before door is 
fully closed)

Increase lockout time.  Refer to DIP switch 
chart.

Data wires reversed at Bodyguard/
DK-12

Reverse data wires at Bodyguard/DK12.

Check voltage on data wires (red and red/
white).

Green LED does not 
illuminate when safety 
beams are blocked

Faulty safety beam receiver

Test the beams and LO-21 with multi-
meter.

Faulty connection on purple and 
gray wire from LO-21

Make contact with the purple and gray 
wires.  Green LED should illuminate.

Improper voltage reading 
on data lines at LO-21

Incorrect wiring at LO-21

Verify correct polarity at terminals 6 and 7 
on Bodyguard.

Faulty LO-21

If data line voltage remains constant at LO-
21 for open and close dpositions and all 
wiring verified, replace faulty LO-21.

©BEA

 | Original Instructions | 

PLEASE KEEP FOR FUR

THER USE - DESIGNED FOR COLOR PRINTING

BEA, the sensor manufacturer, cannot be held responsible for incorrect installations or inappropriate adjustments of the sensor/device; therefore, BEA 
does not guarantee any use of the sensor outside of its intended purpose.
BEA strongly recommends that installation and service technicians be AAADM-certifi ed for pedestrian doors, IDA-certifi ed for doors/gates, and factory-
trained for the type of door/gate system.
Installers and service personnel are responsible for executing a risk assessment following each installation/service performed, ensuring that the sensor 
system installation is compliant with local, national, and international regulations, codes, and standards. 
Once installation or service work is complete, a safety inspection of the door/gate shall be performed per the door/gate manufacturer recommendations 
and/or per AAADM/ANSI/DASMA guidelines (where applicable) for best industry practices.  Safety inspections must be performed during each service 
call – examples of these safety inspections can be found on an AAADM safety information label (e.g. ANSI/DASMA 102, ANSI/DASMA 107). 
Verify that all appropriate industry signage and warning labels are in place. 

BEA INSTALLATION/SERVICE COMPLIANCE EXPECTATIONS

Tech Support: 1-800-407-4545 | Customer Service: 1-800-523-2462

General Tech Questions: Tech_Services@beainc.com | Tech Docs: www.BEAinc.com

Summary of Contents for LO-21

Page 1: ...pletion of installation DO NOT attempt any internal repair of the components All repairs and or component replacements must be performed by BEA Inc Unauthorized disassembly or repair 1 May jeopardize personal safety and may expose one to the risk of electrical shock 2 May adversely affect the safe and reliable performance of the product resulting in a voided warranty Always test the proper operati...

Page 2: ...AC voltage is 50 VAC use the provided 10 000 Ohm resistor to wire in line with the red wire Below are examples of a Keane Monroe Series 2000 swing door operator WIRING TO HYDRAULIC UNIT WIRING TO AC MOTOR If using safety beams blue and green wires must be wired in parallel with the Bodyguard DK 12 connection to the SAF and COM of the door control white required connection optional connection for p...

Page 3: ...nging DIP switch settings These can be set for a time delay of 0 31 seconds See following page for specific DIP switch settings Time Delay begins when motor starts rotating to close door Time Delay DOES NOT stop counting if motor rotation stops Time Delay is only interrupted when door reactivates or safety beams are broken must be set to ensure that red LED remains on for entire door closing cycle...

Page 4: ...1 Incorrect wiring at LO 21 Verify correct polarity at terminals 6 and 7 on Bodyguard Faulty LO 21 If data line voltage remains constant at LO 21 for open and close dpositions and all wiring verified replace faulty LO 21 BEA Original Instructions PLEASE KEEP FOR FURTHER USE DESIGNED FOR COLOR PRINTING BEA the sensor manufacturer cannot be held responsible for incorrect installations or inappropria...

Reviews: