background image

75.5079.10 LO21P 20221219 

 

Page 5 of 8

6.  Once the BODYGUARD-T has learned the “door open” and “door closed” door positions, 

observe the green and red LEDs on the LO21P.  Walk in and out of the BODYGUARD-T 
detection zone while the door is open, and then again when it is closed. Observe the LED 
indications:

7.  Adjust the DIP switch configuration for the correct lock-out time delay:

a. 

Activate the door to the “open” position.

b.  Time the overall door-closing cycle. 
c. 

Refer to the DIP switch configuration chart on the next page to set the desired lock-
out time.

d.  Activate the door again to the “open” position.
e. 

From outside of the BODYGUARD-T detection zone, observe the red LED on the 
BODYGUARD-T while the door is closing.
If the red LED on the BODYGUARD-T is illuminated during the closing cycle, it is 
probably detecting the door at the very last degree or two of door closing, which 
would indicate that the lock-out time needs to be slightly increased.
To resolve, reconfigure the  DIP switches to add 1 second of lock-out time. 

f. 

When the lock-out time is correct, the red LED will not illuminate during the entire 
closing cycle of the door.

8.  Ensure that the BODYGUARD-T detects an object as soon as the door has stopped closing:

a. 

Allow the door to begin closing, and step in behind the doors into the BODYGUARD-
T’s detection zone. 

b.  The BODYGUARD-T’s and LO21P’s red LEDs should illuminate and remain on as soon 

as the door reaches the “fully closed” position, provided that an object remains in the 
BODYGUARD-T’s detection zone.

9.  Set the DIP switches according to the chart below to achieve the desired lock-out time. 

The total lock-out time is the sum total of the DIP switches that are in the ON position. For 
easy reference, use the timetables below. 

Default time is 7 seconds (times are approximate).

SETUP

green 

LED

•  Detection at the BODYGUARD-T while the door is in the open position
•  EAGLE has been triggered
•  On / Off / Hold Open switch is placed in the Hold Open position

If someone steps into the BODYGUARD-T detection zone when the door is open, the 
LO21P’s green LED will illuminate to indicate that the BODYGUARD-T will be connected to 
the activation circuitry of the door, thus holding the door open as long as there is detection.

red 

LED

•  Detection at the BODYGUARD-T while the door is in the closed position
•  EAGLE has been triggered
•  On / Off / Hold Open switch has been activated

When the door is closed, and someone steps into the detection zone of the 
BODYGUARD-T, the 8310-899’s red LED will illuminate, indicating that it will ignore any 
activation signal it receives.  Therefore, the door will remain closed until the BODYGUARD-T 
detection zone is clear.
Once the BODYGUARD-T zone is clear and the door has been activated, it will open and 
remain open for the hold time set by the motion sensor and/or door control, and will also 
hold open during detection at BODYGUARD-T.

Summary of Contents for LO21P

Page 1: ...hen working in public areas Constantly be aware of pedestrian traffic around the door area Always stop pedestrian traffic through the doorway when performing tests that may result in unexpected reactions by the door Always check placement of all wiring before powering up to ensure that moving door parts will not catch any wires and cause damage to equipment Ensure compliance with all applicable sa...

Page 2: ...utside of its intended purpose BEA Inc strongly recommends that installation and service technicians be AAADM certified for pedestrian doors IDA certified for doors gates and factory trained for the type of door gate system Installers and service personnel are responsible for executing a risk assessment following each installation service performed ensuring that the sensor device system performanc...

Page 3: ... II SYSTEM Q DISCONNECT ON SAFETY SIDE May be used on most models of operators red black yellow green blue DATA 7 AUTO 1 15 VAC brown orange purple gray white red white black white 24 V TRANSFORMER OPERATOR OFF HOLD MOTOR SAFETY COMMON ACTIVATION Contacts to open at desired point of inhibiting STALL DOOR CONTROL DATA 6 N C 5 N O 4 COM 3 POWER 2 POWER 1 1 2 3 4 5 6 7 8 1 2 3 4 5 8 7 6 5 4 3 2 1 LO2...

Page 4: ...nits Correct any faults before proceeding If the BODYGUARD T learns a door closed position but does not execute a setup for the door open position place the door in a hold open position With the Universal Remote Control unlock the BODYGUARD T and with the door in the open position press the Magic Wand key and then 2 The BODYGUARD T should begin flashing green to signify a setup If it does not this...

Page 5: ...DYGUARD T s and LO21P s red LEDs should illuminate and remain on as soon as the door reaches the fully closed position provided that an object remains in the BODYGUARD T s detection zone 9 Set the DIP switches according to the chart below to achieve the desired lock out time The total lock out time is the sum total of the DIP switches that are in the ON position For easy reference use the timetabl...

Page 6: ...FF ON OFF 9 ON OFF OFF ON OFF 10 OFF ON OFF ON OFF 11 ON ON OFF ON OFF 12 OFF OFF ON ON OFF 13 ON OFF ON ON OFF 14 OFF ON ON ON OFF 15 ON ON ON ON OFF 16 OFF OFF OFF OFF ON 17 ON OFF OFF OFF ON 18 OFF ON OFF OFF ON 19 ON ON OFF OFF ON 20 OFF OFF ON OFF ON 21 ON OFF ON OFF ON 22 OFF ON ON OFF ON 23 ON ON ON OFF ON 24 OFF OFF OFF ON ON 25 ON OFF OFF ON ON 26 OFF ON OFF ON ON 27 ON ON OFF ON ON 28 OF...

Page 7: ...N HORTON 7000 ON OFF ON KM 2000 ON OFF ON STANLEY MAGIC SWING MAGIC FORCE with safety ON OFF ON DIP 6 ON LO21P expects incoming voltage at the red and black wires while the door is in the open position Typical for DC motors OFF LO21P expects incoming voltage at the red and black wires while the door is in the closed position DIP 7 DIP 8 OFF ON LO21P closes safety circuit yellow wire upon BODYGUARD...

Page 8: ...nd LO21P Door will not close On Off Hold Open switch is in hold open position Place switch in On or Auto position BODYGUARD T is in detection Launch a setup at BODYGUARD T Faulty door control Remove wire from COM and ACT terminal at door control If door does not close replace or repair the faulty control Bodyguard keeps re learning with each door position Incorrect data polarity at BODYGUARD T Ens...

Reviews: