background image

Page 8 of 8  

75.5079.10 LO21P 20221219

TROUBLESHOOTING

Door will not open

All LO21P LEDs are off

Faulty door control

1.  Ensure input power (orange and brown wires) 

is good at LO21P:  
12 – 24 VAC/VDC.

2.  Go directly to door control and jumper COM 

and ACT input. If door opens, proceed to next 
step. If not, replace/repair faulty door control.

3.  Go to LO21P and jumper the red/white wire to 

the black/white wire. 
The green LED on LO21P should come on and 
the door should open. If not, replace LO21P. 
If LED comes on, but door does not open, 
ensure that the blue and green wires are 
properly connected to the door control.

4.  Ensure that the On / Off / Hold Open switch is 

functioning properly.

5.  Verify EAGLE proper operation. Jumper COM 

and N.O. terminals while wires are attached. 
If door does not open, check wiring between 
EAGLE and LO21P.

Faulty LO21P

Faulty On / Off / Hold Open switch

Faulty EAGLE

Faulty wiring

Door will not open

Red LED on at LO21P

BODYGUARD-T in detection

1.  Launch a setup on BODYGUARD-T.

2.  Ensure BODYGUARD-Trelay output is 

programmed to a value of 2 (default is 1).

3.  Verify no breaks in wiring.  

When BODYGUARD-T is in detection, an 
open circuit occurs at the purple and gray 
wires on the LO21P. If there is any break in 
wiring between purple and gray and the 
LO21P, the LO21P will react the same as if the 
BODYGUARD-T were in detection.

BODYGUARD-T improperly programmed

Faulty wiring between BODYGUARD-T 
and LO21P

Door will not close

On / Off / Hold Open switch is in “hold 
open” position

Place switch in On or Auto position.

BODYGUARD-T is in detection

Launch a setup at BODYGUARD-T.

Faulty door control

Remove wire from COM and ACT terminal at door 
control.  If door does not close, replace or repair 
the faulty control.

Bodyguard keeps re-learning with 
each door position

Incorrect data polarity at BODYGUARD-T

Ensure that the white wire goes to terminal 6 of 
BODYGUARD-T, and the red/white wire goes to 
terminal 7 of BODYGUARD-T.

Insufficient voltage switching at red and 
black wire of LO21P

When door is closed, there should be 0 volts 
observed on the red and black wires of LO21P.

When the door is open, voltage should be greater 
than approximately 9 volts. If voltage is not high 
enough at red and black wires when the door 
is open, the LO21P will not be able to send the 
correct data to BODYGUARD-T. 

Polarity must 

also be correct.  The red wire must ALWAYS 
connect to the positive wire of the motor, 
as observed during door open position.  

See 

important note in Wiring Connections (page 2).

As the door is closing, the 
BODYGUARD-T seems to 
reactivate the door to the open 
position as it is seeing the door 
closing

DIP switch 6 at LO21P is set incorrectly

Switch the position of DIP switch 6 and re-test 
the door

Tech Support & Customer Service: 1-800-523-2462

General Tech Questions: techservices-us@BEAsensors.com | Tech Docs: www.BEAsensors.com

©BEA

 | Original Instructions | 

PLEASE KEEP FOR FUR

THER USE - DESIGNED FOR COLOR PRINTING

Can’t find your answer?  Visit www.BEAsensors.com or 
scan QR code for Frequently Asked Questions!

Summary of Contents for LO21P

Page 1: ...hen working in public areas Constantly be aware of pedestrian traffic around the door area Always stop pedestrian traffic through the doorway when performing tests that may result in unexpected reactions by the door Always check placement of all wiring before powering up to ensure that moving door parts will not catch any wires and cause damage to equipment Ensure compliance with all applicable sa...

Page 2: ...utside of its intended purpose BEA Inc strongly recommends that installation and service technicians be AAADM certified for pedestrian doors IDA certified for doors gates and factory trained for the type of door gate system Installers and service personnel are responsible for executing a risk assessment following each installation service performed ensuring that the sensor device system performanc...

Page 3: ... II SYSTEM Q DISCONNECT ON SAFETY SIDE May be used on most models of operators red black yellow green blue DATA 7 AUTO 1 15 VAC brown orange purple gray white red white black white 24 V TRANSFORMER OPERATOR OFF HOLD MOTOR SAFETY COMMON ACTIVATION Contacts to open at desired point of inhibiting STALL DOOR CONTROL DATA 6 N C 5 N O 4 COM 3 POWER 2 POWER 1 1 2 3 4 5 6 7 8 1 2 3 4 5 8 7 6 5 4 3 2 1 LO2...

Page 4: ...nits Correct any faults before proceeding If the BODYGUARD T learns a door closed position but does not execute a setup for the door open position place the door in a hold open position With the Universal Remote Control unlock the BODYGUARD T and with the door in the open position press the Magic Wand key and then 2 The BODYGUARD T should begin flashing green to signify a setup If it does not this...

Page 5: ...DYGUARD T s and LO21P s red LEDs should illuminate and remain on as soon as the door reaches the fully closed position provided that an object remains in the BODYGUARD T s detection zone 9 Set the DIP switches according to the chart below to achieve the desired lock out time The total lock out time is the sum total of the DIP switches that are in the ON position For easy reference use the timetabl...

Page 6: ...FF ON OFF 9 ON OFF OFF ON OFF 10 OFF ON OFF ON OFF 11 ON ON OFF ON OFF 12 OFF OFF ON ON OFF 13 ON OFF ON ON OFF 14 OFF ON ON ON OFF 15 ON ON ON ON OFF 16 OFF OFF OFF OFF ON 17 ON OFF OFF OFF ON 18 OFF ON OFF OFF ON 19 ON ON OFF OFF ON 20 OFF OFF ON OFF ON 21 ON OFF ON OFF ON 22 OFF ON ON OFF ON 23 ON ON ON OFF ON 24 OFF OFF OFF ON ON 25 ON OFF OFF ON ON 26 OFF ON OFF ON ON 27 ON ON OFF ON ON 28 OF...

Page 7: ...N HORTON 7000 ON OFF ON KM 2000 ON OFF ON STANLEY MAGIC SWING MAGIC FORCE with safety ON OFF ON DIP 6 ON LO21P expects incoming voltage at the red and black wires while the door is in the open position Typical for DC motors OFF LO21P expects incoming voltage at the red and black wires while the door is in the closed position DIP 7 DIP 8 OFF ON LO21P closes safety circuit yellow wire upon BODYGUARD...

Page 8: ...nd LO21P Door will not close On Off Hold Open switch is in hold open position Place switch in On or Auto position BODYGUARD T is in detection Launch a setup at BODYGUARD T Faulty door control Remove wire from COM and ACT terminal at door control If door does not close replace or repair the faulty control Bodyguard keeps re learning with each door position Incorrect data polarity at BODYGUARD T Ens...

Reviews: