Page 4 of 4
75.5366.08 UL MAGLOCKS 600lb 20210806
LOCK STATUS RELAY CONTACTS (SPDT)
- Relay dry contacts are rated 1A at 24 VDC for safe operation, DO NOT exceed this
rating.
- If a NO switch is required, connect the wires from the system to Terminal 3 and
Terminal 4.
- If a NC switch is required, connect the wires from the system to Terminal 4 and
Terminal 5.
DOOR STATUS SWITCH (DS versions only)
- Connect the positive (+) lead from the power source to the
black wire of the Door Status Sensor switch.
- Connect the negative (-) lead from the power source to one
end of the light for door status.
- Connect the red or green wire of the Door Status Sensor switch
to the other end of the light for door status.
red = light off with door closed
green = light on with door closed
- Reed switch dry contacts are rated 0.25 amp at 30 VAC/VDC
for safe operation.
Do not exceed this rating.
7 Installation
–
Electrical (cont.)
SWITCHES
+ -
G
1 2 3 4 5
+ - NO C NC
12VDC
24VDC
POWER
SELECTOR
JUMPER
0 - 90 SEC.
RELOCK TIMER
POWER
SUPPLY
+ -
LOCK STATUS RELAY (SPDT)
1
PCB
2
sw
+
-
NC
COM
NO
1
PCB
2
MAGNETIC LOCK
NC
RED
GREEN
BLACK
LIGHT
COM
REED SWITCH
ON
DOOR STATUS SENSOR SWITCH*
* Switch changes state when door is open
NO
BEA Inc., the sensor manufacturer, cannot be held responsible for incorrect installations or incorrect adjustments of the sensor/device; therefore, BEA Inc. does not
guarantee any use of the sensor/device outside its intended purpose.
BEA Inc. strongly recommends that installation and service technicians be AAADM-certifi ed for pedestrian doors, IDA-certifi ed for doors/gates, and factory-trained for the
type of door/gate system.
Installers and service personnel are responsible for executing a risk assessment following each installation/service performed, ensuring that the sensor/device system
performance is compliant with local, national, and international regulations, codes, and standards.
Once installation or service work is complete, a safety inspection of the system shall be performed and documented per the manufacturer’s recommendations or industry
guidelines. Examples of compliance may apply to ANSI 156.10, ANSI 156.19, ANSI/DASMA 102, ANSI/DASMA 107, UL294, UL325, and International Building Code.
BEA, INC. INSTALLATION/SERVICE COMPLIANCE EXPECTATIONS
Tech Support & Customer Service: 1-800-523-2462 | General Tech Questions: techservices-us@BEAsensors.com | Tech Docs: www.BEAsensors.com