48
4233 5000 13
Digital input screens
Cycling through the digital input screens, the following information is displayed:
<d.1>
Service timer reading
<d.2>
Running hours
<d.3>
Actual program version
Parameter screens
<P.1>
Selection between local, remote or LAN
<P.2>
Setting a node ID for CAN control
<P.3>
Settings for IP, gateway and subnet mask
<P.4>
Modifying the service timer
Test screen
<t.1>
Display test
Setting of correct CAN address
To ensure the dryer can be operated by the main controller, it needs to be attributed the right
CAN address.
To change the CAN address, scroll down to <P.2> and press enter. Depending if CAN is
already enabled or not, you will see “On” or “OFF”. Push down again until you see a number
between 1 and 31. Push enter again, and change the CAN address by pushing up or down, to
the following:
•
For dryer number one, this CAN address needs to be set to 11.
•
For the second one, this needs to be set to 12.
Note: If CAN is already enabled, you need to disable it first before you are able to change CAN
address.
Summary of Contents for dMED 025