background image

Icon

Status

Description

Pressure fault

Dryer outlet pressure too low. Manual reset required.

Dew point fault

Dew point too high. Manual reset required.

Pressure and dew
point fault

Dryer outlet pressure too low and dew point too high. Manual reset
required.

Service enabled

A service function has been activated.

Service required

The programmed service interval is reached and maintenance is
required.

Menu structure

Main menu flowchart (full access mode)

Downward navigation through the menus is done by pressing the Enter button. Upward navigation through
the menu is done by pressing the Escape button on the controller. Specific submenus and commands will be
explained in the following chapters. The main screens are referred to as follows:

• Starting screen (ES_1): shows the inlet net pressure and the status of the plant.
• Main menu (ES_2): gives access to the different submenus (see section 

Central controller operation

).

Instruction book

2920 7099 70

23

Summary of Contents for dMED 100

Page 1: ...BeaconMed s Dual medical air purifiers dMED 7 dMED 13 dMED 25 dMED 35 dMED 50 dMED 70 dMED 80 dMED 100 dMED 145 Instruction book...

Page 2: ......

Page 3: ...authorized use or copying of the contents or any part thereof is prohibited This applies in particular to trademarks model denominations part numbers and drawings This instruction book is valid for CE...

Page 4: ...TRODUCTION 9 2 2 AIR FLOW 11 2 3 WSD AND FILTERS 13 2 4 CD DRYER 14 2 5 QDT FILTER 16 2 6 ELECTRICAL DIAGRAMS 16 2 7 OPTIONAL EQUIPMENT 17 3 ES MED Central controller 20 3 1 INTERFACE ICONS AND MENU S...

Page 5: ...DP FILTER CHANGE 73 7 3 CD UNIT DESICCANT CHANGE 74 7 4 QDT FILTER MAINTENANCE 74 7 5 TESTING THE ELECTRONIC DRAIN VALVE 76 8 Problem solving 77 9 Technical data 80 9 1 FUSE VALUES 80 9 2 ELECTRIC CAB...

Page 6: ...in environments or rooms where the sound pressure level reaches or exceeds 90 dB A shall wear ear protectors Never remove or tamper with the safety devices e g safety valves regulators All regulating...

Page 7: ...orbidden to dwell or stay in the risk zone under a lifted load Lifting acceleration and deceleration must be kept within safe limits Wear a safety helmet when working in the area of overhead or liftin...

Page 8: ...ressor full flow safety valves must be installed on the dryer vessels 16 If the maximum pressure of the compressor is higher than the design pressure of the dryer a full flow safety valve must be inst...

Page 9: ...se the correct safety equipment such as safety glasses gloves safety shoes etc 2 Use only the correct tools for maintenance and repair work During use it is possible that tools will become contaminate...

Page 10: ...ponents etc to prevent moisture from entering them e g when steam cleaning 18 Make sure that all sound damping material and vibration dampers e g damping material on the bodywork is in good condition...

Page 11: ...dryer CD dryer to lower the pressure dew point PDP to 40 C 40 F eliminating the risk of condensation and strongly reducing water related problems like bacteria growth The QDT filter reduces hydrocarbo...

Page 12: ...General views dMED general view 1 Air inlet 2 Water separator WSD 3 DD filter 4 PD filter 5 CD dryer 6 QDT filter 7 PDp filter 8 Pressure regulator 9 Safety valve Instruction book 10 2920 7099 70...

Page 13: ...mentioned Always consult the local legislation on this topic since the specifications of the air quality can be different A dMED unit is considered as an active medical device relying on a source of e...

Page 14: ...3 8 F Next is the QDT filter where oil vapour and smells of the dried air are reduced active carbon and where the conversion of CO into CO2 takes place catalyst in QDT Finally the air flows through th...

Page 15: ...2 3 WSD and filters WSD and filters in the air flow WSD and filter overview Instruction book 2920 7099 70 13...

Page 16: ...mg m3 0 01 ppm and particles down to 0 01 micron The filter is equipped with a drain Typical pressure drop over filter is 0 08 bar 1 16 psi when dry and 0 2 bar 2 9 psi when saturated The air flow is...

Page 17: ...sition of the selector valve depends on the condition activated or not of the solenoid valves While the air flows upwards through the tower the desiccant adsorbs the water vapour and the compressed ai...

Page 18: ...DT filter A QDT filter contains active carbon reducing volatile organic compounds VOC and hydrocarbons odours oil vapours to harmless levels A QDT filter contains active carbon and catalyst material c...

Page 19: ...ction drawings provided Available options Electronic drain EWD The electronic drain is optional on the WSD the DD filter and the PD filter The electronic drain is a zero loss electronically operated d...

Page 20: ...D or filters DD and PD before installing the EWD Voltage free contact DD PD and PDp filters A voltage free contact closing at a pressure drop of 0 35 bar 5 08 psi over the filter can be provided The c...

Page 21: ...ol the purity of the air The oil indicator is a calibrated measuring instrument used to detect aerosol mist levels of oil entrainment that may be present in compressed air systems Sensitivity of the i...

Page 22: ...rolling the compressors and dryers 5 Voltage LED Indicates that the voltage is switched on 6 Enter button Confirm action 7 Escape button Go to previous screen or end current action 8 Stop button Not u...

Page 23: ...n Status Description No valid compressor A compressor controller is expected at this CAN address node but not detected No communication No reply from the connected compressor controller within a pre d...

Page 24: ...ed Local backup system Service required The compressor s running hours have surpassed the predefined interval and maintenance must be carried out Isolated User has isolated this compressor controller...

Page 25: ...d maintenance is required Menu structure Main menu flowchart full access mode Downward navigation through the menus is done by pressing the Enter button Upward navigation through the menu is done by p...

Page 26: ...ryer View screen ES_8 enables the user to view the plant information as graph or as 2 line or 4 line inputs 3 2 Central controller ES MED operation Gaining full access to all menus To access certain m...

Page 27: ...After commissioning the plant the ES MED control system must be started see paragraph Starting further in this section During production the system should have been set correctly in the software To ve...

Page 28: ...number of compressors present on your plant and ES should be set On Setting the unit of pressure In the Settings General submenu full access needed see above navigate to Pressure Unit and select the d...

Page 29: ...Master submenu In normal circumstances these settings should not be changed please contact BeaconMed s Parameter Function Min setting Factory setting Max setting Unit Pressure band X High To program...

Page 30: ...rting a new compressor at the interval programmed in Forced Time 2 2 30 days Maximum power down time If ArAF is set to Active e g instead of Infinite then the system will only restart automatically wi...

Page 31: ...having completed the CAN and ES setup described above carry out the following steps 1 Put the compressor s main switch to ON and the local LAN switch to LAN The emergency forced local warning see sect...

Page 32: ...l appear to indicate that the ES MED is operating Stopping and resetting the ES MED To stop a certain compressor see section Stopping in the compressor manual To force all compressors local the ES MED...

Page 33: ...compressors any more The compressors are now in Forced Local Mode even though their local LAN switch may be in LAN position This allows the operator to do maintenance or troubleshooting on the central...

Page 34: ...ry out maintenance on a compressor without transmitting alarms select the ES submenu from the main menu requires full access see above Browse to the compressor that needs to be isolated and press Ente...

Page 35: ...yer pressure or dew point fault or after 200 operating hours the dryer will automatically switch to the backup dryer However also during normal operation it is possible to switch to the backup dryer T...

Page 36: ...hen a dryer fails on low outlet pressure and or high dew point the controller will automatically switch to the backup dryer An icon representing the failure will be displayed on the failing dryer Inst...

Page 37: ...r again it needs first to be reset manually Event history When an alarm is triggered the full situation inputs outputs time stamp is logged into the event history To take a look follow the following s...

Page 38: ...tionally Please contact BeaconMed s Viewing information about the central controller Through the following submenu and pressing More information regarding MAC address software IP settings etc can be v...

Page 39: ...e dryer as well as the pressure at the outlet of the dryer and the dew point The outputs are the alarms or normal status that are transmitted potential free to the hospital control room Closed corresp...

Page 40: ...Inputs Instruction book 38 2920 7099 70...

Page 41: ...6 Carbon dioxide 14 EWD Alarm status side 2 7 Modify 15 Pressure drop over filters side 1 8 Dryer inlet 16 Pressure drop over filters side 2 Outputs 1 Menu 11 Dryer 1 exhaust valve vessel B 2 Setting...

Page 42: ...up cylinder pressure decreases below the predefined limit When this is resolved by successfully replacing the backup cylinders the warning will be automatically reset 2 Dryer 1 2 Dew Point Alarm Occur...

Page 43: ...re part list whereby the error on the failed dryer needs to be reset manually 4 No valid pressure control Occurs when no read out is obtained indicated by stars for the dryer inlet pressure sensor As...

Page 44: ...steps to set a custom IP address gateway and subnet mask After connecting an ethernet cable between your network and the controller the plant can be monitored on line when browsing to the set IP addre...

Page 45: ...Instruction book 2920 7099 70 43...

Page 46: ...ompanied by the red warning LED on the central controller and when applicable also on a compressor controller a problem needs to be remedied 4 alarms can occur alone or simultaneously Per alarm the po...

Page 47: ...nt fault error will disappear automatically 4 All slave compressors in load There is a peak of high flow demand or the plant is not properly sizes resulting in all compressors being required to delive...

Page 48: ...ssors of the plant are not performing to their full capacity Check that maintenance is carried out as required according to section Maintenance and that the drawn current on the amp meter corresponds...

Page 49: ...tion The pressure measured at the outlet of the unit after the regulator exceeds the limits too high or too low Evidently this situation requires immediate attention Causes and remedies This situation...

Page 50: ...1 Service 9 Depressurize vessels 2 Service plan 10 Drying after service 3 Service maintenance 11 Dryer forced operation Instruction book 48 2920 7099 70...

Page 51: ...conomy saving The dryer exhaust valves will be closed when all compressors are stopped or in unload Whenever a compressor is being called to deliver air the dryer will operate in normal operation agai...

Page 52: ...before performing any maintenance 1 Depressurize vessels 3 Activate 2 Remaining time Drying after service Whenever a dryer has been serviced receiving new desiccant it is possible this desiccant is n...

Page 53: ...will be disabled automatically after a preset time 1 Drying forced operation 3 Modify 2 Remaining time Commissioning To ensure the system is in good condition when it s being commissioned this functio...

Page 54: ...4 Installation 4 1 Dimension drawings Instruction book 52 2920 7099 70...

Page 55: ...Instruction book 2920 7099 70 53...

Page 56: ...Instruction book 54 2920 7099 70...

Page 57: ...Instruction book 2920 7099 70 55...

Page 58: ...Instruction book 56 2920 7099 70...

Page 59: ...Instruction book 2920 7099 70 57...

Page 60: ...Instruction book 58 2920 7099 70...

Page 61: ...Instruction book 2920 7099 70 59...

Page 62: ...References on drawings Instruction book 60 2920 7099 70...

Page 63: ...room Reference Name 1 Minimum free area to be reserved for the medical air unit installation Install the equipment on a level floor suitable for taking its weight Provide enough space approximately 8...

Page 64: ...tion of the dMED unit can only be done by trained and certified service personnel The preferred and recommended installation sequence is compressor 3 vessel 2 and dMED 1 The dMED does not require extr...

Page 65: ...ctric diagram delivered with the unit Before switching on the main power supply check the voltage requirements in the technical specifications or on the unit s data plate 4 4 Pictographs Pictographs o...

Page 66: ...will have This flow must not be directed into the air net but needs to be blown off via another way The initial dew point of the air leaving the unit will be higher than normal after starting Since th...

Page 67: ...the start up phase of the compressor may damage the desiccant All valves couplings and pipes used installed after the unit must be free from oil and grease hydrocarbon contamination below 550 mg m2 an...

Page 68: ...ater separator In case of EWD optional Check that no alarm is displayed on the service panel of the EWD 5 and that oil water aerosols and or solid particles are discharged via drain outlet 6 The amoun...

Page 69: ...ize the vessels 3 Stop the dMED ES MED controller If the air treatment unit is stopped for a longer period keep the external inlet and outlet valve closed to avoid moisture from entering the unit Unde...

Page 70: ...icles enter the unit Therefore correct maintenance of the water separator and the filters is crucial Safety precautions Maintenance must be done by trained and certified service personnel Use only aut...

Page 71: ...eaks Check for abnormal noise Check the filter of the pressure dew point sensor for dust and clean if necessary Check the pressure drop over the filters Check if all drains are working properly Monthl...

Page 72: ...ngs are in good shape and free of wear or abuse 6 3 Service kits Service kits Service kits are available offering the benefits of genuine parts while keeping the maintenance budget low The kits compri...

Page 73: ...other used material e g desiccant lubricants cleaning rags machine parts etc must be disposed of in an environmentally friendly and safe manner and in line with the local recommendations and environme...

Page 74: ...se will warn you if the bowl is not fully depressurized If this occurs the bowl should be screwed back and the venting should be repeated 4 Remove the drain valve 3 by unscrewing the retaining nut 5 u...

Page 75: ...in valve 4 by unscrewing the retaining nut 5 underneath the bowl 6 Remove the O ring from the bowl and clean the bowl Position a new O ring on the bowl 7 Remove the O ring from the drain valve and pos...

Page 76: ...ry 4000 hours whichever comes first Its pressure drop will not increase during its useful life Nevertheless the adsorption element must be changed earlier at the first signs of oil vapour and odour Wh...

Page 77: ...lace the o ring between the flange and the head 14 Slowly pressurize the filters 15 Check for leaks A small amount of water based lubricant supplied in the medical cleaning kit may be applied to screw...

Page 78: ...ion Control buttons of EWD 32 Functional test Briefly press the TEST button and check that the valve opens for condensate discharge Checking the alarm signal Close the condensate inlet Press the TEST...

Page 79: ...to prevent an accidental start Close air inlet and outlet valve 2 of the unit The air inlet and outlet valve 2 can be locked during maintenance or repair work as follows Close the valve Using a wrenc...

Page 80: ...Filter clogged Clean the filter bowl and replace the filter element QDT filter Condition Fault Remedy Bad filtration Activated carbon lifetime exceeded Replace the activated carbon at indicated inter...

Page 81: ...int Check connections Check sensors Dew point sensor incorrect measurement Dew point alarm generated too early or too late Check sensors Replace defective parts Faults and remedies ES MED Condition Fa...

Page 82: ...plicable if they are stricter than the values proposed below The voltage drop must not exceed 5 of the nominal voltage It may be necessary to use cables of a larger size than those stated to comply wi...

Page 83: ...compressed air inlet pressure psig See section dMED data Minimum compressed air inlet pressure bar e See section dMED data Minimum compressed air inlet pressure psig See section dMED data Min max amb...

Page 84: ...nt per vessel CD lb 18 1 18 1 18 1 25 6 33 7 Amount of activated carbon per vessel QDT kg 2 0 2 0 3 8 3 8 4 8 Amount of activated carbon per vessel QDT lb 4 4 4 4 8 4 8 4 10 6 Air quality Pharmacopeia...

Page 85: ...dryer mbar 515 530 560 595 820 Pressure drop over dryer psi 7 47 7 69 8 12 8 63 11 89 Time of half a cycle s 180 180 120 120 120 Regeneration time s 145 145 95 95 95 Pressurization time s 35 35 25 25...

Page 86: ...ower VA 124 124 124 166 Net mass kg 219 239 267 354 Net mass lb 483 527 589 780 Air quality Pharmacopeia O2 concentration 20 4 X 21 4 CO2 concentration ppm 500 CO concentration ppm 5 SO2 concentration...

Page 87: ...ncentration ppm 2 Pressure dew point C 31 Pressure dew point F 23 8 Oil vapour mg m 0 1 Taste and odour free Unit dMED 70 dMED 80 dMED 100 dMED 145 Volume flow at dryer inlet l s 94 5 108 135 196 Volu...

Page 88: ...C 31 Pressure dew point F 23 8 Oil vapour mg m 0 1 Taste and odour free Remark When the actual inlet pressure or inlet temperature differs from the reference condition the volume flow will be differe...

Page 89: ...manufacturer 4 The design pressure and temperature of this pressure bearing part must be clearly indicated on the data label 5 If installed the safety valve must correspond with pressure surges of 1 1...

Page 90: ...l CD 7 1627 0009 00 16 10 to 80 I 6 150 8 3 CD 13 1627 0010 00 16 10 to 80 I 6 150 11 7 CD 25 1624 0938 00 16 10 to 80 I 6 150 15 7 CD 35 CD 70 1624 0939 00 16 10 to 80 I 6 150 20 0 CD 50 CD 80 CD 10...

Page 91: ...Devices Directive All components are designed manufactured and inspected according to the European Directive 93 42 EC annex II and art 11 par 3 Overall rating The dMED unit is conform the Medical Dev...

Page 92: ...onformity 1 Contact address Atlas Copco Airpower n v P O Box 100 B 2610 Wilrijk Antwerp Belgium 1 Contact address BeaconMed s Telford Crescent Staveley Derbyshire S43 3PF United Kingdom Instruction bo...

Page 93: ......

Page 94: ...No 2920 7099 70 2012 01 Printed in Belgium www beaconmedaes com...

Reviews: