7.3
CD unit desiccant change
Desiccant for CD unit
Warning
To ensure that the unit always produces pharmacopoeia compliant air, only dedicated and
genuine spare parts must be used.
The installation and maintenance must be done by trained and certified personnel.
Pharmacopoeia compliance
After carrying out any maintenance or repair work, Pharmacopoeia testing must be done
by a local testing company to assure reliable and correct operation of the unit.
When replacing desiccant, make sure that the desiccant is disposed of according to the
local regulations.
Consult the parts list for part numbers.
7.4
QDT filter maintenance
Service
Change the QDT filter element yearly or every 4000 hours, whichever comes first. Its
pressure drop will not increase during its useful life. Nevertheless, the adsorption element
must be changed earlier at the first signs of oil vapour and odour.
When the filter has to process air with a temperature higher than the reference temperature, the filter’s lifetime
will shorten considerably. It is then advisable to oversize the filter.
The air flow of the filter is from the bottom to the top of the filter. Due to the composition of the activated
carbon element, the bag must be placed with the knot at the top of the bag. Observe the correct order of the
bags (activated carbon first, than catalyst)!
If an oil indicator is mounted, the purity of the air is measured. When the indicator shows a fast increase of
oil content in the air, the QDT filter element and the indicator tube have to be replaced.
Instruction book
74
2920 7099 70
Summary of Contents for dMED 100
Page 2: ......
Page 40: ...Inputs Instruction book 38 2920 7099 70...
Page 45: ...Instruction book 2920 7099 70 43...
Page 54: ...4 Installation 4 1 Dimension drawings Instruction book 52 2920 7099 70...
Page 55: ...Instruction book 2920 7099 70 53...
Page 56: ...Instruction book 54 2920 7099 70...
Page 57: ...Instruction book 2920 7099 70 55...
Page 58: ...Instruction book 56 2920 7099 70...
Page 59: ...Instruction book 2920 7099 70 57...
Page 60: ...Instruction book 58 2920 7099 70...
Page 61: ...Instruction book 2920 7099 70 59...
Page 62: ...References on drawings Instruction book 60 2920 7099 70...
Page 93: ......
Page 94: ...No 2920 7099 70 2012 01 Printed in Belgium www beaconmedaes com...