Page 1-88
MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)
Configuring and Browsing the Master Alarm Using the Web Pages
Chapter 1: Introduction
Figure 1-38. Setup Device—Silenced Return Time
NOTE:
This step is used to set the amount of time that the alarm remains silenced.
13. Click on the amount of time that you want between audible alarms.
NOTE:
To comply with the requirements of the City of New York Department of
Buildings; Materials and Equipment Acceptance Division (M.E.A.), do not set
the alarm return time to “never.” Set the alarm to return every 30 minutes.
NOTE:
Silencing or delaying the audible alarm does not clear the alarm; the alarm mes-
sage remains on the display until the alarm condition is remedied.
14. Click in the
N2 Address
window.
NOTE:
This is an option. An RS-485 interface from the alarm to the facility’s building
automation system can be used. If used, both the Master Alarm and the facility’s
building automation system receive alarm signals.
Summary of Contents for MedPlus TotalAlert
Page 370: ...Schematic Wiring Diagram Typical Local Alarm...
Page 371: ...Schematic Wiring Diagram Typical Master Alarm...
Page 372: ...Schematic Wiring Diagram Typical Master Alarm to Master Alarm...
Page 373: ...Schematic Wiring Diagram Typical Area Alarm...
Page 374: ...Schematic Wiring Diagram Typical Master Alarm to Three Area Alarm...
Page 375: ...Schematic Wiring Diagram Typical Master Alarm to Six Area Alarm Combination...