CAUTION:
Maintain the polarity of the source equipment leads between the Master
Alarms, otherwise they may not operate as intended.
CAUTION:
If you are replacing an Area Alarm Module in an Area Alarm that uses the
Network Communications Board and the Ethernet, use the Clear Network
function before you start the procedure. Otherwise, the MedPlus
TotalAlert® Alarm Network will indicate that an error has occurred.
CAUTION:
If you are replacing an Area Alarm Module in a 30-Point Master Alarm
with three Area Alarm Modules, use the Clear Network function before
you start the procedure. Otherwise, the MedPlus TotalAlert® Alarm
Network will indicate that an error has occurred.
CAUTION:
When two or more MedPlus TotalAlert® Alarm Network systems are on
the same Ethernet network but not separated by a router, the alarm will
not operate as intended.
MedPlus TotalAlert® Alarm Network Operation and Maintenance Manual (205728)