28
Part No. 6-847684-00 Rev. D01
Finish Installation
4. The alarm panel’s power supply is
factory installed with a three-wire
harness attached to its right side.
Connect loose end of three wire
harness to male connector on
annunciator module circuit board as
shown in Figure 15. The harness
connector is keyed to prevent incorrect
orientation, however, use care to
ensure correct pin alignment.
Figure 15: Power Supply Wire Harness
Remote Sensors:
1. Remove sensor module from shipping
carton. Each sensor module is
shipped with a wiring pigtail that has a
two-pin polarized connector.
2. Wire nut pigtail to field installed wiring
inside sensor mounting box. Note
polarity of wiring and corresponding
field wiring color or number for later.
3. Join polarized connector in sensor
mounting box to mating connector on
sensor module. Refer to Figure 16.
4. Insert sensor into valve opening in
sensor rough-in. An indexing pin
provides for proper orientation and
prevents gas service cross-
connection. Push sensor all the way
in and secure with (2) #6-32 x 1-1/4”
screws.
Figure 16: Sensor Module Connection
NOTE:
Remove the blue protective netting from the sen-
sor connector.
Sensor Installation
Annunciator Module
Power Supply
Three-wire harness
Front Panel Installation
Valve opening
Sensor
Polarized
connector
Male connector
NOTE:
Field wiring cable shields must be grounded at
only on one end, inside alarm panel back box.
Refer to page 31 for details.
black
red