4-14
MEGA3 NFPA Medical Gas Notification System
4107 9016 59.03
Figure 77: Configuration Screen
Source
signal
inputs
Tabs used for configuration
of source signal input A
Figure 78: Configuration of alarm points
1 = ALARM POINT
To identify the location
where the wires are
landed
2 = GAS MONITORED
To choose the gas to be
monitored
3 = SIGNAL SETTINGS
To select source signal
description
4 = LOCATION
To add a location for
the source signal
4.4.1 Configuring Source Badges
The MEGA3 alarm is designed to allow
the setup and monitoring of 4 source
badges. Each source badge has room for
10 source signal inputs (A-K) (Figure 78).
Four tabs are used for the detailed con-
figuration of each source signal input.
To configure alarm points in the first badge,
touch the [1] button in the numeric display.
The four tabs for each source signal input are
grouped together and named alphabetically
(e.g., A1, A2, A3, A4 / B1, B2, B3, B4 / C1, C2,
C3, C4 / etc.).
Users can scroll to the first tab for each source
signal input by using the right and left ar-
rows at the bottom of the screen. Or, to
jump quickly to the first tab, simply touch
the letter button on the grid on the left that
corresponds to the source signal input (A-K)
(Figure 78).
The first tab for each source signal input is
highlighted and the remainder grayed out
to ensure that users complete the setup in
the correct order. The other three tabs will
become available to you as you advance
through setup.
Note
:
Maximum wired input signals allowed is 40.