4-15
MEGA3 NFPA Medical Gas Notification System
4107 9016 59.03
Figure 79: Alarm Point Tab
To identify the location where the wires are
landed:
1. Touch the tab for the appropriate board
and terminal block. Ex: B10 board, X01
Terminal Block
2. Touch the Save button when you see a
check beside your selection to go auto-
matically to the GAS MONITORED screen.
A2 = Gas Monitored Tab
Figure 80: Gas Monitored Tab
To choose the gas to be monitored:
1. Scroll through the codes using the right
and left arrows at the bottom of the
screen.
2. Touch the tab for the appropriate gas.
3. Touch the Save button when you see a
check beside your selection to go auto-
matically to the SIGNAL SETTINGS screen.
A3 = Signal Settings Tab
Figure 81: Signal Settings Tab
To select source signal input text:
1. Touch the NONE/BLANK tab.
2. Scroll through the options using the
right and left arrows at the bottom of the
screen.
3. Touch the tab for the appropriate option
4. Touch the Save button when you see a
check beside your selection to save the
selection and return to the SIGNAL SET-
TINGS screen.
5. Touch the X button in the upper right to
go automatically to the LOCATION screen.
A1 = Alarm Point Tab