MEGA3 NFPA Medical Gas Notification System
4107 9016 59.03
4.5.3 Initial Setup of an Unconfig-
ured Combination Alarm
The SETUP INFORMATION screen is the first
screen that users will see on an unconfigured
alarm.
(The MAIN screen is the first screen that users
will see on a configured alarm).
Figure 90: Setup Information Screen
Configuration
Button
• Touch the Configuration button.
Entering the Password
The ENTER SECURITY PASSWORD screen ap-
pears.
Figure 91: Entering the Security Password
Note
:
If you would like to change the password,
touch Change Password. Enter a 4-10 digit
password, and touch the Enter button. Con-
firm the new password. Touch the X button
in the upper right to close the SECURITY
PASSWORD screen.
Enter the security password. (The default
password is
121212.
)
• Touch the Enter button.
• Touch Continue to advance to the
CONFIGURATION screen.
• The CONFIGURATION screen will display
as unconfigured and ready for setup.
Primary Settings Tab
The PRIMARY SETTINGS tab allows you to
select the alarm type and initialize boards.
Figure 92: Changing the Security Password
• Touch the PRIMARY SETTINGS tab.