69
6-847718-00 Rev. B00
Set-Up Procedures (Cont.)
Multi-Signal Module
Changing signal options:
1. Loosen two screws on front of alarm
panel. Hinge open front cover.
2. Locate SETUP button on circuit board
of multi-signal module to be adjusted
(Figure 48).
3. Press and release SETUP button.
Audible alarm will chirp and both
green and red indicators for top
location (Signal 1) will illuminate.
4. Using either
!
or
"
buttons, enable
or disable Signal 1 location. When red
indicator is illuminated, location is
ENABLED. Turning off red indicator
disables location. Signal locations can
not be disabled if wired to a closed-
contact circuit.
5. Press and release TEST button on
front of alarm panel. Both green and
red indicators for second location
(Signal 2) will be illuminated.
6. Using either
!
or
"
buttons, enable
or disable Signal 2 location. When red
LED is illuminated, location is enabled.
Turning off red LED disables location.
7. Repeat steps 5 and 6 above for
remaining signal locations (Signal 3, 4,
and 5).
8. Press and release TEST button to
save changes. LEDs will sweep from
top to bottom to indicate end of set-up
sequence has been reached.
9. Multi-signal module will return to
monitoring mode.
NOTE:
If module is idle for more than one minute during
set-up procedure, module will chirp three times,
return to monitor mode and will default to previ-
ous settings. No changes to settings will be
saved.
Set-up must be completed in order for changes to
be saved.
Multi-Signal Module Board
SETUP
button
NOTE:
Audible alarm will chirp with each button push.
TEST
button
Up and down
buttons
Signal 1
Signal 2
Signal 3
Signal 4
Signal 5
Status LEDs
Figure 49: Multi-Signal Module LEDs
Figure 48: Digital Display Programming Buttons
Summary of Contents for TotalAlert 2
Page 1: ...Installation Operation and Maintenance Instructions 6 847718 00 Rev B00...
Page 2: ......
Page 22: ...20 6 847718 00 Rev B00...
Page 97: ...95 6 847718 00 Rev B00 Figure 86 Clear Network Accepted Operation...
Page 99: ...97 6 847718 00 Rev B00 Operation Figure 89 Event Log Cleared...
Page 101: ...99 6 847718 00 Rev B00 Operation Figure 91 Transfer Setup Figure 92 Transfer Setup Complete...
Page 129: ...127 6 847718 00 Rev B00 Troubleshooting Guide Troubleshooting...
Page 130: ...128 6 847718 00 Rev B00...
Page 139: ...137 6 847718 00 Rev B00 Replacement Parts Notes...
Page 143: ......
Page 144: ...2007 BeaconMed s All rights reserved 6 847718 00 Rev B00...