71
6-847718-00 Rev. B00
Operation
Set-Up Procedures (Cont.)
Multi-Signal Module-
Advanced (Cont.)
Setting Audible Alarm Repeat Time and
Display Intensity:
Used to set time interval for reactivation of
audible alarm after alarm MUTE
button
has been pressed.
1. Press and HOLD SETUP button.
Audible alarm will chirp when SETUP
button is first pushed, again after two
seconds and a third time after four
seconds. Release button after third
audible alarm chirp. Multi-signal module
front panel LED indicators will show
current audible alarm repeat time as
shown below:
Indicator Illuminated Repeat Time
None
OFF
Signal 1 - red
1 Min.
Signal 2 - red
5 Min.
Signal 3 - red
15 Min.
Signal 4 - red
30 Min.
Signal 1 - green
1 Hr.
Signal 2 - green
2 Hr.
Signal 3 - green
8 Hr.
Signal 4 - green
12 Hr.
Signal 5 - green
24 Hr.
2. Using either
!
or
"
buttons, select
desired audible alarm repeat time.
3 Press and release TEST button on front
of alarm panel. All LED indicators will
illuminate.
4. Select desired display brightness by
pressing either
!
or
"
buttons. Each
push will increase or decrease
brightness of display. Audible alarm will
chirp one time with each button push
and two times when limit is reached.
NOTE:
To comply with the requirements of the City of
New York Department of Buildings; Materials
and Equipment Acceptance Division (M.E.A.),
set audible alarm repeat time to 30 minutes.
5. Press and release TEST button to save
changes. LEDs will sweep from top to
bottom to indicate end of set-up
sequence.
6. Multi-signal module will return to
monitoring mode.
NOTE:
If module is idle for more than one minute dur-
ing set-up procedure, module will chirp three
times, return to monitoring mode and will default
to previous settings. No changes to settings will
be saved.
Set-up must be completed in order for changes
to be saved.
Summary of Contents for TotalAlert 2
Page 1: ...Installation Operation and Maintenance Instructions 6 847718 00 Rev B00...
Page 2: ......
Page 22: ...20 6 847718 00 Rev B00...
Page 97: ...95 6 847718 00 Rev B00 Figure 86 Clear Network Accepted Operation...
Page 99: ...97 6 847718 00 Rev B00 Operation Figure 89 Event Log Cleared...
Page 101: ...99 6 847718 00 Rev B00 Operation Figure 91 Transfer Setup Figure 92 Transfer Setup Complete...
Page 129: ...127 6 847718 00 Rev B00 Troubleshooting Guide Troubleshooting...
Page 130: ...128 6 847718 00 Rev B00...
Page 139: ...137 6 847718 00 Rev B00 Replacement Parts Notes...
Page 143: ......
Page 144: ...2007 BeaconMed s All rights reserved 6 847718 00 Rev B00...