5. INDICATION
AND
CONTROL
5.1 Battery level LEDs
The battery level LEDs show the voltage level both in back-up mode and in normal
mode. When the LED indicates 20% of the capacity in back-up mode, it means that
the UPS is going to shut down; for the length of backup time left, it will depend on the
load. While when all five LEDs light in normal mode, it means that the battery is fully
charged.
5.2 Special status LEDs
The
Replace Battery
LED would be on when the UPS battery is no longer useful and
must be replaced.
When the
Alarm Off
LEDs comes on, the UPS will not emit beep during back-up mode
or when battery needs to be replaced. However, the low battery alarm and over load
alarm will still sound for urging user to leave computer without any data loss.
The
Charging
LED would be on when the charger is charging the battery. While the
battery voltage is low in normal mode, the charger will keep on quick charging, when the
battery voltage is high, the charger is keeping on for 4 seconds by every 24 seconds for
trickle charging.
The
Boost
LED would be on when the UPS is connecting a low utility voltage. The loads
receive normal power.
The
Buck
LED would be on when the UPS is connecting a high utility voltage. The
loads receive normal power.
5.3 Auto self-test function:
In normal mode of UPS, turn on your computer and push the button on the front panel
for self-test. The UPS will simulate a power outage and transfer your load to the UPS
battery. If low battery warning sounds during the test, it means that the battery set is
weak and requires extended recharge. If replace battery warning sound, it means
that the battery set is damaged and requires replacement.
5.4 Status LED and Alarm Indication:
※
GRN LED, no alarm ------------------------------------------------- City power normal.
※
ORG LED flashing, two beeps / 8 sec. ------------------------ Backup mode.
※
ORG LED flashing, one beep / 4 sec. -------------------------
No load. (Auto shut down after 24 sec.)
※
ORG LED flashing, quick beeping, 4 beeps / sec ---------- Low battery.
※
Red LED flashing, continuous beeping ------------------ Over load.
※
“Replace battery” LED, urgent beeping, 8 beeps / sec ---- Battery Replacement.
5.5 Reset the UPS
If any abnormal condition occurs, and the item 4.2.1 ~ 4.2.3 can not be executed,
please push the button for at least 6 sec. until the buzzer emit continues beeping,
then the UPS is reset.
Under back-up mode, the UPS will be turned off by reset. While under AC mode, the
UPS will go through the procedure of self-test by reset.