BD-050 

BD-050

 

 

1. Introduction: 

 

The UPS is an on-line DC output UPS with the most 
advanced design of universal input, 110V/220V, and 
frequency auto-detect, 47Hz – 70Hz.  With the high 
efficiency switching type converter, the UPS is able to provide 
stable DC 24V output at any input voltage, and zero 
transference from utility power (normal mode) to backup 
mode (battery mode) or from backup mode to normal mode.

 

2. Main 

Feature 

 

 

Micro-processor based design 

 

 

Universal input range (110V / 220V) 

 

 

On-line structure, zero transference 

 

 

Full operation data indication 

 

 

Protection for overload / short-circuit 

 

3. Installation 

Test

 

 

 

3.1  Open the front panel by lifting the bottom edge outward. 

 

 

3.2  Disconnect the LED control cable on main PCB. 

 

 

3.3  Turn off the AC switch and DC switch of UPS. 

 

 

3.4  Connect the I/P power cord and O/P DC 24V cord. 

 

 

3.5  When all connection is OK, please turn on AC switch first and make 

sure that the O/P DC 24V is OK, if not, re-check the connection and 

the AC fuse. 

 

 

3.6  If DC 24V is correct, turn on DC switch and make sure that the DC 

24V is O.K.  Then, turn off AC switch, the DC 24V should be still 

O.K. 

 

 

3.7  Turn on AC switch, and connect the LED control cable on the main 

PCB. 

 

 

3.8  Put back the front panel on the base case of the UPS. 

 

 

3.9  Push the test button for 3 seconds, the “

Replace Battery

” LED 

should be 

OFF

 and “

Back up

” LED should be 

ON

, if not, recheck the 

procedure from 3.4 to 3.8. 

 

 

3.10  Push the test button for 3 seconds again, the UPS should be back to 

normal mode, and either 110VAC or 220VAC LED should be 

ON

 

 

3.11  During the long time utility outage (over 24 hrs), please turn off the 

DC switch, or the battery may become NG because of over 

discharge. 

 

 