background image

4

Pre-Installation Checklist

Combustion Air Supply

The fuel supply piping and tank must provide #1 or #2 
fuel oil at pressure or vacuum conditions suitable for 
the fuel unit (oil pump) on the burner. Refer to fuel unit 
literature in the literature envelope in the burner carton to 
verify allowable suction pressure.

If fuel supply is level with or higher than fuel unit:

When the fuel unit is not required to lift the oil, the 
installation is usually suitable for either a one-pipe or 
two-pipe oil system. The oil pressure at the inlet of 
the fuel unit must not exceed 3 psig.
The fuel unit is shipped with the by-pass plug 
installed. Leave the by-pass plug installed for all 
low/high 

fi

 ring burners, regardless whether one-

pipe (with by-pass loop) or two-pipe. See 

Figure 

9

 for installation of the by-pass loop required for 

one-pipe fuel supply installations. See 

Figure 10

 for 

connections to the fuel unit for two-pipe fuel supply 
installations.

When fuel supply is below the burner fuel unit:

Use a two-pipe oil system when the fuel unit must 
lift the oil more than 8 feet. The return line provided 
by the two-pipe system is needed to minimize the 
effects of air-related problems during operation.

Nozzle Pressure

The burner requires combustion air and ventilation air 
for reliable operation. Assure that the building and/or 
combustion air openings comply with National Fire 
Protection Standard for Oil-Burning Equipment, NFPA 
31. For appliance/burner units in con

fi

 ned spaces, the 

room must have an air opening near the top of the room 
plus one near the 

fl

 oor, each with a free area at least 

one square inch per 1,000 Btu/hr input of all fuel burning 
equipment in the room. For other conditions, refer to 
NFPA 31 (CSA B1139-M91 in Canada).
If there is a risk of the space being under negative 
pressure or of exhaust fans or other devices depleting 
available air for combustion and ventilation, the 
appliance/burner should be installed in an isolated room 
provided with outside combustion air.

Clearances

With the burner installed in the appliance, there must be 
adequate space in front of and on the sides of the burner 
to allow access and operation. Verify that the clearance 
dimensions comply with all local codes and with the 
appliance manufacturer’s recommendations.

Fuel Supply

Adequate Combustion and 
Ventilation Air Supply Required

Failure to provide adequate air supply could result in 

asphyxiation, explosion or 

fi

 re hazards.

The burner cannot properly burn the fuel if it is not 
supplied with a reliable combustion air source.
Follow the guidelines in the latest editions of the 
NFPA 31 and CSA-B139 regarding providing 
adequate air for combustion and ventilation.

y

y

Oil Supply Pressure 
Control Required

Damage to the 

fi

 lter or pump seals could cause oil 

leakage and a 

fi

 re hazard.

The oil supply inlet pressure to the burner 

cannot 

exceed 3 psig

.  

Do not install valves in return line.

Insure that a pressure limiting device is installed in 
accordance with the latest edition of NFPA 31. 
Gravity Feed Systems: Always install an anti-siphon 
valve in the oil supply line or a solenoid valve (RWB 
Part # 21789) in the pump/nozzle discharge tubing 
to provide backup oil 

fl

 ow cut-off protection. 

y

y
y

y

Correct Nozzle and Flow 
Rate Required

Incorrect nozzles and 

fl

 ow rates could 

result in impaired combustion, under-

fi

 ring, over-

fi

 ring, sooting, puff-back of 

hot gases, smoke and potential 

fi

 re or 

asphyxiation hazards. 

Use only nozzles having the brand, 

fl

 ow rate (gph), 

spray angle and pattern speci

fi

 ed by the appliance 

manufacturer.

Follow the appliance manufacturer’s speci

fi

 cations for 

the required pump outlet pressure for the nozzle, since 

this affects the 

fl

 ow rate. 

Nozzle manufacturers calibrate nozzle 

fl

 ow rates at 

100 psig.
This burner utilizes pressures higher than 100 psig, 
so the actual nozzle 

fl

 ow rate will be greater than the 

gph stamped on the nozzle body. (Example: An 8.00 
gph nozzle at 150 psig = 9.80 gph and at 300 psig = 
13.86 gph)
For typical nozzle 

fl

 ow rates at various pressures 

refer to Table 1.

y

y

y

Section: Pre-Installation Checklist

Summary of Contents for CF1400

Page 1: ...tion start up or service work Save this manual for future reference y y y Incorrect installation adjustment or misuse of this burner could result in death severe personal injury or substantial propert...

Page 2: ...which your burner ap pliance is installed Make sure Air ventilation openings are clean and unob structed Nothing is blocking burner inlet air openings No combustible materials are stored near the heat...

Page 3: ...e read all instructions before proceeding Follow all instructions completely This equipment must be installed adjusted and started by a qualified service agency that is licensed and experienced with a...

Page 4: ...ed in an isolated room provided with outside combustion air Clearances With the burner installed in the appliance there must be adequate space in front of and on the sides of the burner to allow acces...

Page 5: ...he appliance dimensions are smaller than recommended reduce the firing rate accordingly Table 1 Nozzle Capacities Rated gph 100 psig Pressure Pounds per square inch 125 140 150 175 200 250 275 300 3 0...

Page 6: ...ing rate required On the CF2300 there are two tube arrangements available Tube A 7 0 to 19 9 GPH per Figure 3 Tube B 10 0 to 19 9 GPH per Figure 3 The CF2300 maximum firing capacity depends on the fir...

Page 7: ...loss of burner operation resulting in no heat an unplanned process interruption work stoppage and the potential for frozen plumbing or other cold weather property damage Protect Against Dust and Mois...

Page 8: ...he end of the nozzle line leaving the nut loosely placed so the plates can be moved Connect the high voltage leads from the ignition transformer to the electrodes Check and adjust if necessary the cri...

Page 9: ...s than dimension D in Figure 8 Thread the pipe into the flange Secure the burner to the appliance by tightening the nuts on the burner flange mounting studs 1 2 3 4 5 6 Figure 7 Adjusting Plate Assy F...

Page 10: ...ump k Return line to oil tank m One pipe by pass loop 3 8 p Air bleed valve Figure 9 One pipe Oil Flow with B Pump SK9940 Figure 10 Two pipe Oil Flow with B Pump SK9939 Use continuous lengths of heavy...

Page 11: ...s energized A flame should be established within the factory set trial for ignition time lockout time Lockout The control has shut down for one of the following safety reasons The trial for ignition l...

Page 12: ...equence The control will continue to Recycle each time the flame is lost until it reaches a pre set time allotment The control will then go into Hard Lockout instead of recycle This feature prevents e...

Page 13: ...13 CF1400 CF2300 Burner Manual Figure 13 Typical Wiring 7505P Section Wire the Burner...

Page 14: ...de The burner starts at Low goes to High after the flame stabilization 1 2 3 4 5 6 a period Flame is extinguished when the load is satisfied or a limit opens and the burner is sent to Motor Off Delay...

Page 15: ...tart up Professional Installation and Service Required Incorrect installation and mishandling of start up could lead to equipment malfunction and result in asphyxiation explosion or fire This burner m...

Page 16: ...0 6 17 0 60 16 0 7 18 0 70 17 0 8 19 0 80 18 0 9 20 0 90 19 0 100 20 0 B 0 12 5 0 1 13 0 10 10 0 2 14 0 20 13 0 3 15 0 30 14 0 4 16 0 40 15 0 5 17 0 50 16 0 6 18 0 60 17 0 7 18 5 70 18 0 8 19 0 80 18...

Page 17: ...to its low fire setting This initial setting should be adequate for starting the burner at low fire Once the burner is in operation the air setting will be adjusted for best performance as discussed l...

Page 18: ...stment Vapor Filled Appliance Allow the unit to cool off and all vapors to dissipate before attempting another start Oil Flooded Appliance Shut off the electrical power and the oil supply to the burne...

Page 19: ...Burner Move the low fire hold switch to the low fire hold position to hold burner in low fire when started Verify that the air adjusting cam Figure 17 item d has been set to the initial low fire air...

Page 20: ...3 12 44 DIA 51498 13 92 DIA 51630 16 00 DIA Flange A Flange B Flange C Check the pump pressure and cutoff function Check primary control safety lockout timing Check ignition system for proper operatio...

Page 21: ...21 CF1400 CF2300 Burner Manual SK9930 3 2 4 5 6 1 SK9931 8 9 7 Section Replacement Parts Figure 19a Burner Replacement Parts...

Page 22: ...5994U 5201301U 51204U 5201302U 14 Sight glass All models 31346 31346 15 Head assembly 5978 51203 16 Electrode assembly All models 51212 51212 17 Ignition leads 8 1 4 long 11 3 4 long 15 1 4 long 19 1...

Page 23: ...23 CF1400 CF2300 Burner Manual Figure 19b Burner Replacement Parts Continued SK9936 SK9932 SK9930 14 13 12 10 20 11 21 22 23 15 16 17 18 19...

Page 24: ...copy of warranty form 61545 please choose one of the following options Visit our website at www beckettcorp com warranty Email your request to rwb customer service beckettcorp com Write to R W Beckett...

Reviews: