background image

 

 

Basic information 

 

BK8000 

11 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Insulation test 
 
 
 
 
 
 
 
PE power contacts 

The connection between bus couplers and bus terminals is automatically 
effected by latching the components together. The K bus is responsible for 
passing data and power to the electronic components of the bus terminals. 
In the case of digital bus terminals, the field logic receives power via the 
power contacts. Latching the components together has the effect that the 
series of power contacts constitutes a continuous power track. Please refer 
to the circuit diagrams of the bus terminals: some bus terminals do not loop 
these power contacts through, or not completely (e.g. analog bus terminals 
or 4-channel digital bus terminals). Each power input terminal interrupts the 
series of power contacts and constitutes the beginning of a new track. The 
bus coupler can also be used to supply power to the power contacts.  
 
The power contact labeled "PE” can be used as protective earth or ground. 
This contact stands proud for safety reasons and can carry short-circuit 
currents of up to 125 A. Note that in the interests of electromagnetic 
compatibility the PE contacts are capacitively connected to the supporting 
track. This may lead to spurious results and even damage to the terminal 
when you test the insulation (e.g. insulation test for breakdown using a 
230 V mains supply to the PE line). You should therefore disconnect the 
PE line on the bus coupler while you carry out insulation tests. You can 
disconnect other power supply points for the duration of the test by drawing 
the power supply terminals out from the remaining row of terminals by at 
least 10mm. If you do this, there will be no need to disconnect the PE 
connections.  
 
The protective earth power contact ("PE”) may not be used for any other 
connections. 
 
 

 

Electrical data 

 

 

The electrical data of the RS 485 bus coupler is listed in this chapter. The 
bus coupler is set to a baud rate of 38400 baud. Addresses from 0 to 99 
can be set by means of two address selectors on the coupler. The 
following table provides an overview of all data. 

 

Technical data 

BK8000 

Voltage supply 

24 V DC   (20 ...29 V DC) 

Input current 

70 mA + (total K-Bus current)/4 
500 mA max. 

Output current K-Bus 

1750 mA max. 

Number of bus terminals 

64 

Digital peripheral signals 

256 inputs/outputs 

Analog peripheral signals 

128 Ein-/ Ausgänge 

Maximum number of bytes 

512 Byte I and 512 Byte O 

Station adress 

selectable up to 99 via DIP switches 

Baud rate 

38400 Baud 

Power contact voltage 

24 V DC / AC 

Power contact current load 

10 A 

Dielectric strength 

500 Veff (Power contact / supply voltage) 

Weight approx. 

170g 

Operating temperature 

0°C ... +55°C 

Storage temperature 

-20°C ... +85°C 

Relative humidity 

95%, no condensation 

Vibrations/shock resistance

conforms to IEC 68-2-6 / IEC 68-2-27 

EMC resistance  burst / ESD

conforms to EN 50082 (ESD, Burst) / EN 50081 

Installation position 

any 

Type of protection 

IP20 

 

Current consumption on the  
K-Bus 

For operation of the K-bus electronics, the bus terminals require energy 
from the K-bus that is supplied by the bus coupler. Refer to the catalog or 
the corresponding data sheets of the bus terminals for details of the K-bus 

Summary of Contents for BK8000

Page 1: ...Bus coupler with RS485 interface BK8000 Technical Documentation Version 1 2 2006 10 30...

Page 2: ...Connection 8 K bus contacts 8 Supply isolation 8 The operating modes of the bus coupler 9 Mechanical construction 10 Electrical data 10 The peripheral data in the process image 12 Starting operation...

Page 3: ...cked for consistency with performance data standards or other characteristics None of the statements of this manual represents a guarantee Garantie in the meaning of 443 BGB of the German Civil Code o...

Page 4: ...ed and nullify the liability of Beckhoff Automation GmbH Description of safety symbols The following safety symbols are used in this documentation They are intended to alert the reader to the associat...

Page 5: ...ventional terminal as the cabling level in the switch cabinet the switch cabinet can be made smaller The Beckhoff bus terminal system combines the advantages of a bus system with the functionality of...

Page 6: ...isolation Potential input terminal Power contacts RS485 bus coupler BK8000 Power supply for the bus coupler X1 X10 Bus couplers for various fieldbus systems You can use a variety of bus couplers to at...

Page 7: ...ith spring terminals can be used to supply power to the peripherals The spring terminals are connected in pairs to the power contacts The power supply to the power contacts has no connection to the po...

Page 8: ...xchange of data between the bus coupler and the bus terminals Part of the data exchange takes place via a ring structure within the K bus Disengaging the K bus for example by pulling on one the bus te...

Page 9: ...to test the attached bus terminals the bus terminal test and read in the configuration from which it constructs an internal structure list which is not accessible from outside If an error occurs the b...

Page 10: ...can remove them without effort if you first release the latching mechanism by pulling the orange tab You should carry out work on the bus terminals and the bus coupler only while they are switched off...

Page 11: ...disconnect other power supply points for the duration of the test by drawing the power supply terminals out from the remaining row of terminals by at least 10mm If you do this there will be no need to...

Page 12: ...e oriented The processing of analog signals is always byte oriented and analog input and output values are stored in memory in a two byte representation The values are held as SIGNED INTEGER or twos c...

Page 13: ...s no contradictions is said to be consistent The following consistency is required here 1 The high byte and low byte of an analog value word consistency 2 The control status byte and the corresponding...

Page 14: ...he pattern of flashes as follows Flashing code Fast flashingq Start of the error code First slow sequence Error code Second slow sequence Error argument Error code Error argument Description 1 pulse 0...

Page 15: ...the serial communication link The 4 communication LEDs indicate the status of RS 485 transfer The operating states are indicated by the WD RX TX and ERROR LEDs WD RX TX ERROR RS 485 LED Operating sta...

Page 16: ...hed from the PC s serial interface to the bus coupler This OCX can be used by all programming languages that operate on the basis of the Microsoft Component Object Model COM specifications You will fi...

Page 17: ...ned from Beckhoff RS 485 transmission Fundamental characteristics of physical data transmission per RS 485 Network topology Linear bus active bus terminator at both ends stubs are possible Medium Scre...

Page 18: ...0 operates as the master and the slave bus coupler must be assigned the address 1 Request In the request the master sends the process output data to be transferred to the slave In the response the sla...

Page 19: ...INTEL format The checksum is generated by adding up the contents of the individual bytes complete response string without checksum byte Any occurring overflow is ignored Status byte of the bus coupler...

Page 20: ...ock Bus terminal 0 1 None POS06 KL3002 Channel 1 2 3 None POS06 KL3002 Channel 2 4 0 POS01 KL1002 Channel 1 4 1 POS01 KL1002 Channel 2 4 2 POS02 KL1002 Channel 1 4 3 POS02 KL1002 Channel 2 4 4 POS03 K...

Page 21: ...70 p Start identifier Byte 3 0x05 3 input data words Byte 4 0x12 Returned message ident Byte 5 0x00 Master address 0 Byte 6 0x Status byte Byte 7 0xXX Data byte 0 Byte 8 0xXX Data byte 1 Byte 12 0xXX...

Page 22: ...l input POS17 2 channel digital input POS18 2 channel digital output POS19 2 channel digital output POS20 2 channel analog output POS21 End terminal In the default settings RS485 RS232 CANopen DevicNe...

Page 23: ...Area for bit oriented data digital inputs Relative byte address Bit position Process image in the control unit Position in the block 4 0 I4 POS02 4 1 I4 POS02 4 2 I4 POS03 4 3 I4 POS03 4 4 I4 POS04 4...

Page 24: ...t significant bits are irrelevant Using the KS2000 configuration software it is possible to insert the third byte into the process image for any chosen channels The least significant byte has control...

Page 25: ...econdary process image This representation is not available in the bus coupler s default setting The KS2000 software is needed The meanings of the registers and of the status bytes are explained in th...

Page 26: ...here Beckhoff Headquarters Beckhoff Automation GmbH Eiserstr 5 33415 Verl Germany phone 49 0 5246 963 0 fax 49 0 5246 963 198 e mail info beckhoff com web www beckhoff com Beckhoff Support Support off...

Reviews: