16 

BK8000 

 

RS 485 Coupler BK8000 

 

 

System presentation 

 

General 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Beckhoff KS8000: 
BKcom-OCX 
 
 
 

The BK8000 bus coupler enables the establishment of a simple data bus 
working on a RS 485 transfer basis. By using repeater, up to 99 bus 
coupler can be connected to a bus. The RS 485 coupler is usually 
connected to the PC via the serial interface. For the case that the PC does 
not have a RS 485 interface the use of a interface converter RS232/RS485 
is possible. 
 
Communication with the bus coupler is based on the master/slave 
principle, i.e. there is only one central station (the master), which controls 
access. The slaves are only permitted to send at the master's request. The 
master must request (poll) the data of the slaves (bus couplers) cyclically. 
At the same time, the station is assigned a station address (adjustable by 
rotary switch on the bus coupler) by way of which the master is able to 
address the respective station. Here, the master is always assigned the 
address 0, and the address 1-99 can be used by the slaves. 
 
During the exchange of data with the bus couplers, complete process 
images are always exchanged, i.e. the master sends the complete output 
data to the bus couplers and receives the input data of the bus terminals 
back from the couplers. 
 
A software driver for Windows95/NT is available for communication with 
the bus coupler. This „Beckhoff KS8000: Bkcom-OCX“ provides 
functionality with which a simple connection can be established from the 
PC's serial interface to the bus coupler. This OCX can be used by all 
programming languages that operate on the basis of the Microsoft 
Component Object Model (COM) specifications. You will find further 
explanations in the manual on the „KS8000: BKcom-OCX“. 
 

Master/Slave 
Communication between 
two bus couplers 

It is possible to establish autonomous master/slave communication 
between two bus couplers. To do this, the master bus coupler must be set 
with the station address 0 and the slave bus coupler must be assigned the 
address 1. This enables a simple "complementary" exchange of data 
between two couplers. During such a data transfer, the master transfers its 
input data to the output terminals of the slave and outputs the slave's input 
data to its own output terminals. In this case, attention must be paid to 
ensuring that all data is complementary, i.e. the master must transfer the 
number of output data words to the slave that the slave possesses as input 
data words. The master must receive the same number of input data words 
as the number that it is capable of forwarding to the terminals as data 
output words. 
 

Setting the station 
addresses 

The station address is set by means of the rotary switches on the left side 
of the bus couplers. The address is set as a decimal number. The top 
rotary switch is the units power and the bottom one is the tens power of the 
address (example: station address 18: bottom rotary switch =1, top rotary 
switch = 8). The bus coupler must be reset (by brief interruption of the 
power supply or by software reset) to ensure that the rotary switch settings 
are stored by the bus coupler.  
 

Address selector 

Address-

selector

 

Summary of Contents for BK8000

Page 1: ...Bus coupler with RS485 interface BK8000 Technical Documentation Version 1 2 2006 10 30...

Page 2: ...Connection 8 K bus contacts 8 Supply isolation 8 The operating modes of the bus coupler 9 Mechanical construction 10 Electrical data 10 The peripheral data in the process image 12 Starting operation...

Page 3: ...cked for consistency with performance data standards or other characteristics None of the statements of this manual represents a guarantee Garantie in the meaning of 443 BGB of the German Civil Code o...

Page 4: ...ed and nullify the liability of Beckhoff Automation GmbH Description of safety symbols The following safety symbols are used in this documentation They are intended to alert the reader to the associat...

Page 5: ...ventional terminal as the cabling level in the switch cabinet the switch cabinet can be made smaller The Beckhoff bus terminal system combines the advantages of a bus system with the functionality of...

Page 6: ...isolation Potential input terminal Power contacts RS485 bus coupler BK8000 Power supply for the bus coupler X1 X10 Bus couplers for various fieldbus systems You can use a variety of bus couplers to at...

Page 7: ...ith spring terminals can be used to supply power to the peripherals The spring terminals are connected in pairs to the power contacts The power supply to the power contacts has no connection to the po...

Page 8: ...xchange of data between the bus coupler and the bus terminals Part of the data exchange takes place via a ring structure within the K bus Disengaging the K bus for example by pulling on one the bus te...

Page 9: ...to test the attached bus terminals the bus terminal test and read in the configuration from which it constructs an internal structure list which is not accessible from outside If an error occurs the b...

Page 10: ...can remove them without effort if you first release the latching mechanism by pulling the orange tab You should carry out work on the bus terminals and the bus coupler only while they are switched off...

Page 11: ...disconnect other power supply points for the duration of the test by drawing the power supply terminals out from the remaining row of terminals by at least 10mm If you do this there will be no need to...

Page 12: ...e oriented The processing of analog signals is always byte oriented and analog input and output values are stored in memory in a two byte representation The values are held as SIGNED INTEGER or twos c...

Page 13: ...s no contradictions is said to be consistent The following consistency is required here 1 The high byte and low byte of an analog value word consistency 2 The control status byte and the corresponding...

Page 14: ...he pattern of flashes as follows Flashing code Fast flashingq Start of the error code First slow sequence Error code Second slow sequence Error argument Error code Error argument Description 1 pulse 0...

Page 15: ...the serial communication link The 4 communication LEDs indicate the status of RS 485 transfer The operating states are indicated by the WD RX TX and ERROR LEDs WD RX TX ERROR RS 485 LED Operating sta...

Page 16: ...hed from the PC s serial interface to the bus coupler This OCX can be used by all programming languages that operate on the basis of the Microsoft Component Object Model COM specifications You will fi...

Page 17: ...ned from Beckhoff RS 485 transmission Fundamental characteristics of physical data transmission per RS 485 Network topology Linear bus active bus terminator at both ends stubs are possible Medium Scre...

Page 18: ...0 operates as the master and the slave bus coupler must be assigned the address 1 Request In the request the master sends the process output data to be transferred to the slave In the response the sla...

Page 19: ...INTEL format The checksum is generated by adding up the contents of the individual bytes complete response string without checksum byte Any occurring overflow is ignored Status byte of the bus coupler...

Page 20: ...ock Bus terminal 0 1 None POS06 KL3002 Channel 1 2 3 None POS06 KL3002 Channel 2 4 0 POS01 KL1002 Channel 1 4 1 POS01 KL1002 Channel 2 4 2 POS02 KL1002 Channel 1 4 3 POS02 KL1002 Channel 2 4 4 POS03 K...

Page 21: ...70 p Start identifier Byte 3 0x05 3 input data words Byte 4 0x12 Returned message ident Byte 5 0x00 Master address 0 Byte 6 0x Status byte Byte 7 0xXX Data byte 0 Byte 8 0xXX Data byte 1 Byte 12 0xXX...

Page 22: ...l input POS17 2 channel digital input POS18 2 channel digital output POS19 2 channel digital output POS20 2 channel analog output POS21 End terminal In the default settings RS485 RS232 CANopen DevicNe...

Page 23: ...Area for bit oriented data digital inputs Relative byte address Bit position Process image in the control unit Position in the block 4 0 I4 POS02 4 1 I4 POS02 4 2 I4 POS03 4 3 I4 POS03 4 4 I4 POS04 4...

Page 24: ...t significant bits are irrelevant Using the KS2000 configuration software it is possible to insert the third byte into the process image for any chosen channels The least significant byte has control...

Page 25: ...econdary process image This representation is not available in the bus coupler s default setting The KS2000 software is needed The meanings of the registers and of the status bytes are explained in th...

Page 26: ...here Beckhoff Headquarters Beckhoff Automation GmbH Eiserstr 5 33415 Verl Germany phone 49 0 5246 963 0 fax 49 0 5246 963 198 e mail info beckhoff com web www beckhoff com Beckhoff Support Support off...

Reviews: