Parameterization and commissioning
BK9053, BK9103
28
Version: 2.3.0
4.4
IP address
Usually the IP address is specified by the PROFINET controller and therefore does not need to be set in the
bus coupler. The bus couplers are addressed via the PROFINET-Name which can be set using various
procedures (see
).
In exceptional cases it makes sense to give the bus coupler an IP address in advance (without connecting
PROFINET), e.g. to access the couplers via KS2000 Software and Ethernet.
4.4.1
IP address and PROFINET name
The IP address can be set using three different procedures, and these will be described in more detail below.
Procedure
Explanation
Necessary components
KS2000
Addressing using the KS2000
configuration software and DIP switches
[
KS2000 configuration software and KS2000 cable
BootP
BootP-Server
DHCP
DHCP-Server
4.4.2
Configuration with KS2000
The KS2000 configuration software (from version 3.2.8) can be used to set the TCP/IP address in a dialog
box, or it can be written directly into the registers. DIP switches 9 and 10 (for BK9050 DIP switches 1 and 2
in blue) should both be OFF (0) before switching on.
Table 100
Register
High-Byte
Low-Byte
0
IP-Byte 2
IP-Byte 1
1
Not used
IP-Byte 3
Default
Byte
Default value (hex)
Default value (dec)
1
0xAC
172
dec
2
0x10
16
dec
3
0x11
17
dec
4
(DIP switch)
(0 to 255
dec
)
Sample
Fig. 14: DIP switch
Switch no.
1
2
3
4
5
6
7
8
9
10
Valence
1
2
4
8
16
32
64
128
-
-
In this example
ON
OFF
OFF ON
OFF
OFF
ON
ON
OFF
OFF
Value
1
0
0
8
0
0
64
128
-
-
Total=201