Holding times
Table 4: Capacity and switch-off times at different discharge currents.
Discharge current [A]
Time to switch-off [s]
Usable energy [Wh]
0.5
3750
12.50
1.0
1900
12.67
1.5
1215
12.15
2.0
900
12.00
2.5
650
10.83
3.0
450
9.00
3.5
320
7.47
4.0
200
4.67
4.5
34
1.02
Fig. 4: Hold time without temperature and ageing effects.