Configuration
CU8130-0120
35
Version: 1.0
Setting or function
Value range Default
value
Description
Turn UPS off wait time [s] Depends on
hardware
(see table
below)
180
The PC must have properly shut down within this
time. An internal timer in the UPS measures the time
from when the OS began to shut down. Once this
time has elapsed, the UPS switches off its outputs in
order to save battery charge. Make sure that you
have not selected too short a time for this.
The available delay times differ from one device to
another. The times are read out from the device, and
are placed in the ComboBox. The UPS service must
be configured and started up with the appropriate
UPS model to make this possible.
Advanced...
-
-
Dialog with advanced shutdown or end session
settings for systems without Soft-Power-Off feature
(S5) (e.g. NT4). For additional info see: Advanced
settings dialog. This option is not available on
systems supporting Soft-Power-Off feature
(deactivated).
Factory Defaults
-
-
Restores default settings.
OK
-
-
Saves all settings and closes the dialog. Don't forgett
to apply the changes at the Beckhoff UPS
Configuration dialog too.
Cancel
-
-
Discards all editable changes and closes the dialog.
Delay times for switching off the UPS in seconds:
• Beckhoff USB UPS: 20, 30, 45, 60, 120, 180, 300, 600