Configuration
CU8130-0120
39
Version: 1.0
bError
: This output is set if an error occurred when executing the function.
nErrId
: Supplies the ADS error number or the command-specific error code (table) when the
bError
output is
set.
Error Codes
Error description
0x0000
No error
0x8001
UPS configuration error. It is possible that the UPS is
not configured correctly or that no UPS is configured
at all.
0x8002
Communication error. Communication with the UPS
was interrupted.
0x8003
Error during the reading of the status data.
stStatus
: Structure with the status information of the UPS (type:
).
Not every UPS device can supply all the status information. Some devices, for example, cannot supply the
BatteryLifeTime
or
BatteryReplace
status.
Example:
Online data with status information of a UPS: