Commissioning
"CX1190 UPS" tab:
Enable Automatic Shut Down:
If this switch is selected, then TwinCAT is stopped after an adjustable retention time, and "Windows XPe" is
shut down. Device 1 (here the CX1100) is switched off after the retention time has elapsed. Even when the
power fails for very short periods (<<10s) the system shuts down and the CX is switched off.
Problem:
If the voltage returns after TwinCAT has stopped but while "Windows XPe" is still in the process of
shutting down, the CX remains on, but "Windows XPe" remains stopped.
The UPS is fully charged again. The voltage must remain switched off for long enough for the UPS to switch
off, and only after this will reboot take place.
Configuration 2:
"Enable Automatic Shutdown"
and
"No Abort" are active:
CX1100-09xx
28
Version: 1.4
Summary of Contents for CX1100-09 Series
Page 1: ...Hardware Documentation CX1100 09xx UPS for Embedded PCs CX10x0 1 4 2015 07 02 Version Date...
Page 2: ......
Page 15: ...Fitting and wiring CX1100 0910 UPS Module CX1100 0920 UPS Module CX1100 09xx 15 Version 1 4...
Page 24: ...Commissioning The retention times are CX1100 09xx 24 Version 1 4...