Mounting and wiring
EL33xx-00x0
65
Version: 4.2
4.13.2
EL3312 - Connection
Fig. 49: EL3312
Earthed thermocouples
Observe for earthed thermocouples: Differential inputs max. ± 2 V to ground!
Current carrying capacity of the input contacts
The maximum permitted current on the signal-relevant terminal points (inputs, GND) is 40 mA (if ap-
plicable).
EL3312 - Connection
Terminal point No.
Comment
Input +TC1
1
Input +TC1
Input +TC2
2
Input +TC2
GND
3
Ground (internally connected with terminal point 7)
Shield
4
Shield (internally connected to terminal point 8)
Input -TC1
5
Input -TC1
Input -TC2
6
Input -TC2
GND
7
Ground (internally connected with terminal point 3)
Shield
8
Shield (internally connected to terminal point 4)