Product overview
EL3632
13
Version: 2.8
2.2
Technical data
Technical data
EL3632
Number of inputs
2
Measuring range
preset ±5 V up to 25 kHz, ±250 mV up to 10 Hz
Supply voltage
24 V
DC
via power contacts
U
EXCITE
U
V
-1 V typ.
Sensor state monitoring
yes, through monitoring of the bias voltage
Supply current I
EXCITE
typ. 2 mA/4 mA/8 mA (separately adjustable for both
channels)
Input filter limit frequency
analog parameterisable 5
th
order low-pass filter up to
25 KHz
typ. 0.05 Hz high-pass
Max. sampling rate
50 kSamples/s
Input
single ended
AC coupling
0.05 Hz typ.
Resolution
16 bit
Measuring error
0,5%
Supply voltage for electronic
via the E-bus
Current consumption via E-bus
typ. 220 mA
Configuration
via TwinCAT System Manager
Weight
approx. 65 g
Permissible ambient temperature range during
operation
0°C ... + 55°C
Permissible ambient temperature range during
storage
-25°C ... + 85°C
Permissible relative humidity
95 %, no condensation
Dimensions (W x H x D)
approx. 15 mm x 100 mm x 70 mm (width aligned:
12 mm)
on 35 mm mounting rail conforms to EN 60715
Vibration/shock resistance
conforms to EN 60068-2-6 / EN 60068-2-27,
see also
installation instructions for terminals with
increased mechanical load capacity [
EMC immunity/emission
conforms to EN 61000-6-2 / EN 61000-6-4
Protection class
IP20
Installation position
variable
Approval
CE