Commissioning
EL3773
88
Version: 2.5
Fig. 102: Linking of 2-bit variable to additional task
Example
of voltage measurement with EL3773:
Channel 1; Limit 1 and Limit 2 enabled, Limit 1 = 100 V, Limit 2 = 200 V, representation: signed integer
Entry in index (Limit 1):
(100 V / 410 V) x 2
16
/ 2 - 1 =
7991
dec
Entry in index (Limit 2):
(200 V / 410 V) x 2
16
/ 2 - 1 =
15983
dec
Output:
Input channel 1
Index
Index
50 V
0x01
hex
, (Limit 1, limit value undershot)
0x01
hex
, (Limit 2, limit value undershot)
100 V
0x03
hex
, (Limit 1, limit value reached)
0x01
hex
, (Limit 2, limit value undershot)
150 V
0x02
hex
, (Limit 1, limit value exceeded)
0x01
hex
, (Limit 2, limit value undershot)
210 V
0x02
hex
, (Limit 1, limit value exceeded)
0x02
hex
, (Limit 2, limit value exceeded)
4. Provision in the process data
The influencing parameters can be changed in the CoE of the respective channel.
Fig. 103: User settings and vendor calibration in the CoE online directory