Commissioning
EL3773
95
Version: 2.5
6.6.2
Configuration data
Index 80p0 AI Settings (for p = 0...5, corresponding to channel 1...6)
Index (hex) Name
Meaning
Data type
Flags
Default
80p0:0
AI Settings
Maximum subindex
UINT8
RO
> 24 <
80p0:07
Limit 1 enabled
BOOLEAN
RW
FALSE
80p0:0A
Enabling of the user calibration
BOOLEAN
RW
FALSE
80p0:0B
Enabling of the vendor calibration
BOOLEAN
RW
TRUE
80p0:13
First limit value for setting the status bits
INT16
RW
0
dec
80p0:14
Second limit value for setting the status bits
INT16
RW
0
dec
80p0:15
This object determines the digital filter settings.
The possible settings are sequentially numbered.
0: 200 Hz
1: 500 Hz
2: 1000 Hz
3: 1500 Hz
4: 2500 Hz
5: 5000 Hz
6: 15000 Hz
See note below:
UINT16
RW
2500 Hz (4)
80p0:17
User calibration offset
INT16
RW
0
dec
80p0:18
User calibration gain
INT16
RW
16384
dec
Note
The filter characteristics are set via index 0x8000:15
The filter frequencies are set for all channels centrally via index 0x8000:15 (channel 1). All
other corresponding indices 0x80p0:15 have no parameterization function!
Index 80pF AI Vendor data (for p = 0...5, corresponding to channel 1...6)
Index (hex) Name
Meaning
Data type
Flags
Default
80pF:0
AI Vendor data
Maximum subindex
UINT8
RO
> 2 <
80pF:01
Calibration offset
Offset (vendor calibration)
INT16
RW
-
80pF:02
Calibration gain
Gain (vendor calibration)
INT16
RW
-
Summary of Contents for EL3773
Page 1: ...Documentation EL3773 Power Monitoring Oversampling Terminal 2 5 2018 03 13 Version Date...
Page 2: ......
Page 6: ...Table of contents EL3773 6 Version 2 5...
Page 39: ...Mounting and wiring EL3773 39 Version 2 5 Fig 29 Other installation positions...
Page 41: ...Mounting and wiring EL3773 41 Version 2 5 Fig 31 Block diagram...
Page 47: ...Commissioning EL3773 47 Version 2 5 Fig 38 Incorrect driver settings for the Ethernet port...