Commissioning
EL3783
139
Version: 1.1
5.6.2
Configuration data
Index 80p0 AI Settings (for p = 0...5, corresponding to channel 1...6)
Index (hex) Name
Meaning
Data type
Flags
Default
80p0:0
AI Settings
Maximum subindex
UINT8
RO
> 24 <
80p0:07
Enable limit
Limit 1 enabled
BOOLEAN
RW
FALSE
80p0:0A
Enable user calibration Enabling of the user calibration
BOOLEAN
RW
FALSE
80p0:0B
Enable vendor calibra-
tion
Enabling of the vendor calibration
BOOLEAN
RW
TRUE
80p0:13
Limit 1
First limit value for setting the status bits
INT16
RW
0
dec
80p0:14
Limit 2
Second limit value for setting the status bits
INT16
RW
0
dec
80p0:17
User calibration offset
User calibration offset
INT16
RW
0
dec
80p0:18
User calibration gain
User calibration gain
INT16
RW
16384
dec
Index F80D AI Device Settings
Index (hex) Name
Meaning
Data type
Flags
Default
F80D:0
AI Device Settings
Maximum subindex
UINT8
RO
> 18 <
F80D:11
Current range
100:
Measuring range 1 A – no automatic switchover
500:
Measuring range 5 A no automatic switchover
600: Dynamic 0 – fast switching
601: Dynamic 1
602: Dynamic 2
603: Dynamic 3 – inert switching
INT16
RW
1 A (100)
F80D:12
DCTimeStampShift
Distributed Clocks Time Stamp Shift
INT16
RW
0
Index 80pF AI Vendor data (for p = 0...5, corresponding to channel 1...6)
Index (hex) Name
Meaning
Data type
Flags
Default
80pF:0
AI Vendor data
Maximum subindex
UINT8
RO
> 9 <
80pF:01
Calibration offset
Offset (vendor calibration) voltage
or 1 A range
INT16
RW
0
80pF:02
Calibration gain
Gain (vendor calibration) voltage
or 1 A range
INT16
RW
16384
80pF:03
Calibration phase off-
set
reserved
INT16
RW
0
80pF:04
Calibration offset
range 1
reserved
INT16
RW
0
80pF:05
Calibration gain range
1
reserved
INT16
RW
16384
80pF:06
Calibration phase off-
set range 1
reserved
INT16
RW
0
80pF:07
Calibration offset
range 2
Offset Range 2 (Herstellerabgleich)
INT16
RW
0
80pF:08
Calibration gain range
2
Gain Range 2 (Herstellerabgleich)
INT16
RW
16384
80pF:09
Calibration phase off-
set range 2
reserved
INT16
RW
0