Commissioning
EL47xx
109
Version: 2.7
5.4.1
TwinCAT 3 procedure
From TwinCAT 3.1 build 4012 and using the revision as below specified in the configuration, the integrated
ScopeView recognizes in its variable browser that the oversampling data is an array package and activates
ForceOversampling automatically. The array as a whole must be selected using
AddSymbol
(see description
in the next section).The extended PDO name provides the basis for this. Since a specific revision of the
respective terminal ScopeView is able to detect the array type of a set of variables autonomous.
Terminal
Revision
EL4732
all
EL4712
all
EL3783
EL3783-0000-0017
EL3773
EL3773-0000-0019
EL3751
all
EL3742
all
EL3702
all
EL3632
all
EL2262
all
EL1262-0050
all
EL1262
all
EP3632-0001
all
EPP3632-0001
all
Recording a PLC Variable with the TwinCAT 3 – ScopeView
By a precondition of an already created TwinCAT 3 – project and a connected PLC with an oversampling
able terminal/box within the configuration it will be illustrated how an oversampling variable can be
represented by the Scope (as a standard part of the TwinCAT 3 environment). This will be explained by
means of several steps based on an example project “SCOPE_with_Oversampling“ as a standard PLC
project.
Step 1: Adding a project „Scope YT“
The example project “SCOPE_with_Oversampling“ has to be added a TwinCAT Measurement – project
“Scope YT project” (C) by right click (A) and selection (B) “Add” → “New Project..”. Then “Scope for OS” will
be entered as name. The new project just appears within the solution explorer (D).
Summary of Contents for EL47 Series
Page 1: ...Documentation EL47xx Analog output terminal with oversampling 2 7 2020 02 27 Version Date...
Page 2: ......
Page 33: ...Mounting and wiring EL47xx 33 Version 2 7 Fig 23 Other installation positions...
Page 70: ...Commissioning EL47xx 70 Version 2 7 Fig 73 Incorrect driver settings for the Ethernet port...
Page 149: ...Commissioning EL47xx 149 Version 2 7 Fig 184 Process data tab SM1 EL47xx...