Diagnosis - Diag Messages
EL70x1
236
Version: 4.4
Text ID
Type
Place
Text (English only)
Cause
0x8001
Error
System
Error: 0x%X, 0x%X, 0x%X
General error; parameters depend on event. See device
documentation for interpretation.
0x8002
Error
System
Communication aborded
0x8003
Error
System
Configuration error: 0x%X, 0x
%X, 0x%X
General; parameters depend on event.
See device documentation for interpretation.
0x8100
Error
General
Error bit set in the status word
0x8101
Error
General
Mode of operation incompatible with the PDO interface
0x8102
Error
General
Invalid combination of Inputs
and Outputs PDOs
Invalid combination of input and output PDOs
0x8103
Error
General
No variable linkage
No variables linked
0x8104
Error
General
Terminal-Overtemperature
The internal temperature of the terminal exceeds the pa-
rameterized error threshold. Activation of the terminal is
prevented
0x8105
Error
General
PD-Watchdog
Communication between the fieldbus and the output
stage is secured by a Watchdog. The axis is stopped au-
tomatically if the fieldbus communication is interrupted.
- The EtherCAT connection was interrupted during opera-
tion
- The Master was switched to Config mode during opera-
tion
0x8135
Error
General
Cycle time has to be a multiple
of 125 µs
The IO or NC cycle time divided by 125 µs does not pro-
duce a whole number
0x8200
Error
Communication
Error while writing
0x8201
Error
Communication
No communication to field-side
(Auxiliary voltage missing)
- There is no voltage applied to the power contacts
- A firmware update has failed
0x82FF
Error
Communication
Boot mode not activated
0x8300
Error
Encoder
Error while setting the position
0x8301
Error
Encoder
Encoder increments not configured
0x8302
Error
Encoder
Feedback-Error
The amplitude of the resolver is too small
0x8400
Error
Drive
Drive incorrectly configured
0x8401
Error
Drive
Limitation of the calibration velocity
0x8402
Error
Drive
Emergency stop activated
0x8403
Error
Drive
ADC Error
Error during current measurement in the ADC
0x8404
Error
Drive
Overcurrent
Overcurrent in phase U, V or W
0x8405
Error
Drive
Modulo position invalid
0x8406
Error
Drive
DC-Link undervoltage (Error)
The DC link voltage of the terminal is lower than the pa-
rameterized minimum voltage. Activation of the output
stage is prevented
0x8407
Error
Drive
DC-Link overvoltage (Error)
The DC link voltage of the terminal is higher than the pa-
rameterized maximum voltage. Activation of the output
stage is prevented
0x8408
Error
Drive
I2T-Model Amplifier overload
(Error)
- The amplifier is being operated outside the specification
- The I2T-model of the amplifier is incorrectly parameter-
ized
0x8409
Error
Drive
I2T-Model motor overload (Er-
ror)
- The motor is being operated outside the parameterized
rated values
- The I2T-model of the motor is incorrectly parameterized
0x8415
Error
Drive
Modulo factor invalid
Summary of Contents for EL7031
Page 1: ...Documentation EL70x1 Stepper Motor Terminals 4 4 2017 08 18 Version Date...
Page 2: ......
Page 6: ...Table of contents EL70x1 6 Version 4 4...
Page 48: ...Mounting and wiring EL70x1 48 Version 4 4 Fig 32 Other installation positions example 2...
Page 96: ...Commissioning EL70x1 96 Version 4 4 Fig 90 Incorrect driver settings for the Ethernet port...
Page 179: ...Commissioning EL70x1 179 Version 4 4 Index 7020 POS Outputs Ch 1...
Page 203: ...Commissioning EL70x1 203 Version 4 4 Index 7020 POS Outputs Ch 1...