Commissioning
EL922x
141
Version: 1.0
Index 1C33 SM input parameter
Index (hex) Name
Meaning
Data type
Flags
Default
1C33:0
SM input parameter
Synchronization parameters for the inputs
UINT8
RO
0x20 (32
dec
)
1C33:01
Sync mode
Current synchronization mode:
• 0: Free Run
• 1: Synchron with SM 3 Event (no outputs
available)
• 2: DC - Synchron with SYNC0 Event
• 3: DC - Synchron with SYNC1 Event
• 34: Synchron with SM 2 event (outputs
available)
UINT16
RW
0x0000 (0
dec
)
1C33:02
Cycle time
Cycle time (in ns):
• Free Run: Cycle time of the local timer
• Synchron with SM 2 Event: Master cycle time
• DC mode: SYNC0/SYNC1 Cycle Time
UINT32
RW
0x000F4240
(1000000
dec
)
1C33:03
Shift time
Time between SYNC0 event and reading of the in-
puts (in ns, only DC mode)
UINT32
RO
0x00000384
(900
dec
)
1C33:04
Sync modes sup-
ported
Supported synchronization modes:
• Bit 0: free run is supported
• Bit 1: Synchron with SM 2 Event is supported
(outputs available)
• Bit 1: Synchron with SM 3 Event is supported
(no outputs available)
• Bit 2-3 = 01: DC mode is supported
• Bit 4-5 = 01: Input shift through local event
(outputs available)
• Bit 4-5 = 10: Input shift with SYNC1 event (no
outputs available)
• Bit 14 = 1: dynamic times (measurement
through writing of 0x1C33:08)
UINT16
RO
0x8001 (32769
dec
)
1C33:05
Minimum cycle time
Minimum cycle time (in ns)
UINT32
RO
0x00002710
(10000
dec
)
1C33:06
Calc and copy time
Time between reading of the inputs and availability of
the inputs for the master (in ns, only DC mode)
UINT32
RO
0x00000000 (0
dec
)
1C33:07
Minimum delay time
UINT32
RO
0x00000384
(900
dec
)
1C33:08
Command
• 0: Measurement of the local cycle time is
stopped
• 1: Measurement of the local cycle time is
started
The entries 0x1C33:03, 0x1C33:06, 0x1C33:09 are
updated with the maximum measured values.
For a subsequent measurement the measured val-
ues are reset.
UINT16
RW
0x0000 (0
dec
)
1C33:09
Maximum delay time
Time between SYNC1 event and reading of the in-
puts (in ns, only DC mode)
UINT32
RO
0x00000384
(900
dec
)
1C33:0B
SM event missed
counter
Number of missed SM events in OPERATIONAL (DC
mode only)
UINT16
RO
0x0000 (0
dec
)
1C33:0C
Cycle exceeded
counter
Number of occasions the cycle time was exceeded in
OPERATIONAL (cycle was not completed in time or
the next cycle began too early)
UINT16
RO
0x0000 (0
dec
)
1C33:0D
Shift too short counter Number of occasions that the interval between
SYNC0 and SYNC1 event was too short (DC mode
only)
UINT16
RO
0x0000 (0
dec
)
1C33:20
Sync error
The synchronization was not correct in the last cycle
(outputs were output too late; DC mode only)
BOOLEAN
RO
0x00 (0
dec
)