Diagnostics
EL922x
151
Version: 1.0
8.2
Text ID’s EL922x
TextId
Hex
Type (en)
Place (En) MessageText (En)
Add. comment
0x1600 Information I/O General Cooling down time still
active, channel %d
0x4611 Warning
I/O General Exceeding the maximum
sum of current (max. %d A)
0x4612 Warning
I/O General Undervoltage detected,
channel %d
0x4613 Warning
I/O General Parameter-value is not
supported by this variant of
terminal, channel %d
0x4614 Warning
I/O General Parameter-value not
allowed and was reduced
automatically, channel %d
0x470E Warning
Overtemperature in device
0x817F Error
General
internal hardware error
(error code)
error code:
11 = missing input voltage channel 1
12 = missing input voltage channel 2
21 = faulty redundant current measurement
channel 1
22 = faulty redundant current measurement
channel 2
31 = overtemperature channel 1
32 = overtemperature channel 2
41 = measurement error channel 1
42 = measurement error channel 2
51 = wiring error, cable break Channel 1 or
input
52 = wiring error, cable break Channel 2 or
input
0x8620 Error
I/O General Undervoltage detected,
channel %d tripped
0x8621 Error
I/O General Overvoltage detected,
channel %d tripped
0x8622 Error
I/O General Reverse current detected,
channel %d tripped
0x8623 Error
I/O General Short circuit detected,
channel %d tripped
0x8624 Error
I/O General Overload detected, channel
%d tripped