Product description
EP1918
12
Version: 1.1.0
3.3
Technical data
Product designation
EP1918-0002
Fieldbus
EtherCAT
Number of inputs
8
Connecting the inputs
M12
Status display
8 (one green LED per input), 5 diagnostic LEDs, 2 LEDs for Us/Up,
2 LEDs for EtherCAT Link/Act
Response time
(read input/write to E-bus)
typically: 3 ms,
maximum: see fault response time
Watchdog time
adjustable from 2 ms to 60 s
Fault response time
≤ watchdog time
Cable length between sensor and EtherCAT Box
Unshielded: 100 m max. (at 0.75 or 1 mm²)
Shielded: 100 m max. (at 0.75 or 1 mm²)
Output current of the clock outputs
(
Input Power Mode
parameter: Diag Testpulse)
typically 10 mA
Output current of sensor supply
(
Input Power Mode
parameter: PowerMode A/B)
max. 250 mA
Max. output current clock outputs / sensor supply in the
event of an error
max. 3 A (the duration depends on the overtemperature-related shutdown of
the output driver)
Input process image
7 bytes (via FSoE if using the default project)
Output process image
6 bytes (via FSoE if using the default project)
Supply voltage for the EP1918
24 V
DC
(–15% / +20%)
Current consumption U
S
(wired with 8 potential-free contacts)
8 channels occupied: typically 100 mA
0 channels occupied: typically 91 mA
(provide 4 A fuse)
Current consumption U
P
(wired with 8 potential-free contacts)
8 channels occupied: approx. 60 mA
0 channels occupied: approx. 35 mA
(provide 4 A fuse)
Power dissipation of the EtherCAT Box
typically 3.8 watts
Electrical isolation (between the channels)
no
Electrical isolation
(between the channels and EtherCAT)
yes
Insulation voltage (between the channels and Ether-
CAT, under common operating conditions)
Insulation tested with 500 V
DC
Dimensions (W x H x D)
30 mm x 126 mm x 26.5 mm
Housing material
PA66-GV 30 (WELLAMID)
Flame Class: V-0
Sealing compound
Polyurethane PU552L
Flame Class: V-0
Weight
approx. 170 g
Permissible ambient temperature
(operation)
-25 °C to +60 °C
Permissible ambient temperature
(transport/storage)
-40°C to +85°C
Permissible air pressure
(operation/storage/transport)
750 hPa to 1100 hPa
(this is equivalent to an altitude of approx. -690 m to 2450 m above sea level
assuming an international standard atmosphere)
Inadmissible operating conditions
TwinSAFE EtherCAT boxes must not be used under the following conditions:
• under the influence of ionizing radiation (exceeding the natural
background radiation)
• in corrosive environments
EMC immunity / emission
conforms to EN 61000-6-2 / EN 61000-6-4 (EMC Zone B)
Vibration resistance
conforms to EN 60068-2-6
5 Hz ≤ f < 8.4 Hz (3.5 mm peak)
8.4 Hz ≤ f < 150 Hz (10 m/s
2
peak)
Shock resistance
conforms to EN 60068-2-27
15 g with pulse duration 11 ms in all three axes
Protection class (when screwed together)
IP67 (according to EN 60529)
Correct installation position
variable
Approvals
CE, TÜV SÜD