Operation
EP1918
20
Version: 1.1.0
Contact
Voltage
1
Control voltage Us, +24 V
DC
(provide a 4 A fuse)
2
Peripheral voltage Up, +24 V
DC
(provide a 4 A fuse)
3
GND Us
4
GND Up
Connecting the functional earth
The contacts of the M8 plug connectors can conduct a maximum current of 4 A.
Two LEDs indicate the status of the supply voltages.
NOTE
Do not confuse the power port with EtherCAT port!
Never connect the power cables (M8, 24 V
DC
) to the green-marked EtherCAT sockets of the EtherCAT Box
Modules. This can cause the destruction of the modules!
Control voltage Us
The fieldbus and the processor logic are supplied from the 24 V
DC
control voltage Us. The control voltage is
electrically isolated from the fieldbus circuitry.
Peripheral voltage Up
The peripheral voltage Up supplies the digital clock outputs and the safe inputs.
Redirection of the supply voltages
The power IN and OUT connections are bridged in the module. Hence, the supply voltages Us and Up can
be passed from EtherCAT Box to EtherCAT Box in a simple manner.
CAUTION
Note the maximum current!
Also ensure when forwarding the supply voltages Us and Up that the maximum permissible current of 4 A
for each contact of the M8 plug connector is not exceeded!