Product overview
Fig. 8: Switch-off ramp - t
Valve curve
Feature bit
must be set in order to activate the valve curve.
The following parameters can be set:
Name
Regis-
ter
Value range
Description
Overlap threshold value - x
1
0 to 1000
The overlap range ends at this process data
value; the resolution is 0.1% (as a fraction of
32767)
Overlap output value - y
1
0 to 1000
The maximum output current in the overlap
region; the resolution is 0.1% (with reference
to the output current that has been set in
register
Bend compensation -threshold
value- x
2
0 to 1000
The bend compensation range ends at this
process data value; the resolution is 0.1% (as
a fraction of 32767)
Bend compensation - output value -
y
2
0 to 1000
The maximum output current in the bend
compensation region; the resolution is 0.1%
(with reference to the output current that has
been set in register
)
Area compensation - threshold
value - x
3
0 to 1000
The area compensation region ends at this
process data value; the resolution is 0.1% (as
a fraction of 32767)
The characteristic curve is divided into four regions:
I
Overlapping
II
Bend compensation
III, III'
Area compensation
IV
End region
KL2535, KL2545
16
Version: 2.0.0